Plan Review Notes
Plan Review Notes For Permit 19041027
Permit Number 19041027
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-30 15:11:13PLUMBING 1ST REVISION REVIEW**DENIED**
  
 NOTE: THIS BUILDING CONSTRUCTED IN 2006 WAS BUILT UNDER
 THE FAIR HOUSING ACT (FHA) THE APPROVED PLAN ON RECORD
 PROVIDE INFORMATION THAT HIS PLAN IS NOW MISSING.
 PLEASE FEEL FREE TO CALL AND DISCUSS IF NEEDED
  
  
 1) THE MEASUREMENT FROM THE REFRIGERATOR WALL TO THE
 NEW ISLAND IS MISSING ON THIS REVISED PLAN. SHT. A300
 OF THE CURRENT APPROVED PLAN LISTED AS 3'6" (42") UNDER
 FHA 7.7 THE MIN REQUIRED SPACE FROM THE EDGE OF THE
 REFRIGERATOR TO THE LEAD EDGE OF THE COUNTER TOP AND OR
 CABINET MUST BE 40". PLEASE PROVIDE WHAT THE
 MEASUREMENT IS. FBC 107.2.1
  
 2) PROVIDE CLEAR FLOOR SPACES @ ALL KITCHEN FIXTURES/
 APPLIANCES TO INCLUDE. KITCHEN SINK, REFRIGERATOR,
 DISHWASHER, STOVE, AND THE RANGE. PLEASE REFER TO FHA
 7.4, 7.5, 7.6
  
  