Plan Review Notes
Plan Review Notes For Permit 19040945
Permit Number 19040945
Review Stop M
Sequence Number 2
Notes
Date Text
2019-05-20 16:43:152ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19040495
 5/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 1ST REVIEW COMMENTS #2, 3, & 4 PRINTED BELOW STILL
 EXIST- PLEASE COMPLY.
  
 2) SHEET 1: PLEASE PROVIDE A SCOPE OF WORK FOR
 MECHANICAL WITH CORRELATING DRAWINGS AND DETAILS ON THE
 PLAN.
  
 3) SHEET 1: IDENTIFY ALL NEW COOKING APPLIANCES ON THE
 PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 917.2 FBC M.
  
 4) SHEET 1: CLARIFY IF A NEW KITCHEN EXHAUST HOOD AND
 EXHAUST DUCT ARE TO BE INSTALLED AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS. SHOW THE EXHAUST DUCT
 RUN AND TERMINATION LOCATION ON THE PLAN. PLEASE NOTE
 MAKEUP AIR MAYBE REQUIRED PER SECTION 505.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  