Plan Review Notes For Permit 19040882 |
Permit Number |
19040882 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-04-18 10:12:20 | RE-ROOF BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- FLAT ROOF ASSEMBLY TO BE INSTALLED I SNOT CLEAR. | | SKETCH PROVIDED SHOWS "BUR HOT-MOPPED ON WOOD DECK A | | 1/2" PERLITE". SELECTED ASSEMBLY W-79 IS FOR A | | NON-INSULATED ASSEMBLY. REVISE/CLARIFY AS REQUIRED. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | NOTE: | | SEPARATE PERMITS REQUIRED FOR ROOF EQUIPMENT | | RE-INSTALLATION. SEC. 102.8 CITY AMENDMENTS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|