2019-04-24 08:12:44 | GAS 1ST REVIEW**DENIED** |
| |
| 1) PLANS/ SUBMITTAL DOCUMENTS THAT BEAR THE NAME, TITLE |
| BLOCK AND OR LICENSE NUMBER OF A DESIGN PROFESSIONAL |
| SHALL BE WET SIGNED AND SEAL. FAC 61G15-23.001. FL ST |
| 471,481. ALL OTHER PLANS/ SUBMITTAL DOCS SHALL BE |
| SIGNED AND DATE MY PERSON TAKING RESPONSIBILITY. |
| |
| 2) WHAT PIPING SIZE AND MATERIAL IS ABOVEGROUND? SHOW |
| THE TYPE OF ALL PIPE MATERIAL BEING INSTALLED, ALL PIPE |
| SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 3)SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE |
| REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION. |
| 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. |
| |
| 4)AT SOME POINT YOU SYSTEM CHANGES TO .5 LB. PLEASE |
| SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED |
| TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. |
| |
| 5)I THIS A NEW OR EXISTING GAS METER/ SYSTEM? PLEASE |
| CLARIFY. IF EXISTING THE BTU LOAD OF THE EXISTING GAS |
| SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE |
| SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. |
| IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3. |
| |
| 6) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| PROPER PIPE SIZE AND BTU LOAD. |
| |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| |