2019-05-08 16:48:31 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| 2. SHOW SIZE OF TAPPED FEEDER CONDUCTORS FBC 107.2.1 |
| |
| 3. SHOW SIZE OF GENERATOR FEEDER. FBC 107.2.1 |
| |
| 4. ONE-LINE DIAGRAM SHOWS 3 MAINS AND 3 EXISTING PANELS |
| THEN ANOTHER ONE-LINE DIAGRAMS SHOWS 1 MAIN AND PANEL |
| BEING REMOVED. WHICH IS IT? FBC 107.2.1 |
| |
| 5. PLANS SHOW 60KW GENERATOR BUT PERMIT SAYS 22KW |
| GENERATOR? PLEASE CLARIFY. FBC 107.2.1 |
| |
| 6. TRANSFER SWITCH SHOWN IN CUT SHEETS IS RATED AT |
| 100AMPS. MINIMUM 400AMP RATED TRANSFER SWITCH REQUIRED. |
| NEC 110.3B |
| |
| 7. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF GENERATOR |
| AND TRANSFER SWITCH. FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |