Plan Review Notes For Permit 19040793
Permit Number 19040793
Review Stop E
Sequence Number 1
Notes
Date Text
2019-04-30 07:09:08ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION OF EXISTING SERVICE
 INCLUDING ALL LOADS. FBC 107.2.1 NEC 220
  
 2. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF NEW
 MTS/PANEL WITH KIRK KEY SYSTEM AND GENERATOR TAP BOX.
 MUST BE UL OR OTHER NRTL LISTED. FBC 107.2.1 NEC 90.7,
 110.2, 110.3B
  
 3. PROVIDE DOCUMENTATION SHOWING COMPLIANCE WITH
 ARC-FLASH MITIGATION FOR OCP 1200AMPS OR HIGHER. NEC
 240.87A&B (MUST BE SIGNED/SEALED FROM ENGINEER).
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved