Plan Review Notes For Permit 19040741 |
Permit Number |
19040741 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-07-12 06:44:43 | 1) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | EXISTING SYSTEM IS PROPERLY SIZED. SUBMIT A GAS PIPING | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | THE SECTION. I HAVE INCLUDED A COPY OF THE MOST RECENT | | GAS DRAWING ON FILE IN THE APPLICATION PACKAGE TO BE | | USED AS REFERENCE ONLY. FGC SECS. 401.4, 401.8, 402.1, | | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, | | G2413.2, G2413.3. WPB AMEND. TO FBC SEC. 107.1.3RD | | REQUEST. | | 2) SHOW THE SIZES AND TYPE OF PIPE MATERIAL BEING | | INSTALLED FOR THE RANGE AND THE TANKLESS WATER HEATER. | | WPB AMEND. TO FBC SEC. 107.2.1. 3RD REQUEST. | | PLEASE CALL THIS REVIEWER TO REVIEW THESE COMMENTS | | PRIOR TO RESUBMITTAL. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|