Plan Review Notes
Plan Review Notes For Permit 19040741
Permit Number 19040741
Review Stop G
Sequence Number 3
Notes
Date Text
2019-07-12 06:44:431) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. I HAVE INCLUDED A COPY OF THE MOST RECENT
 GAS DRAWING ON FILE IN THE APPLICATION PACKAGE TO BE
 USED AS REFERENCE ONLY. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3. WPB AMEND. TO FBC SEC. 107.1.3RD
 REQUEST.
 2) SHOW THE SIZES AND TYPE OF PIPE MATERIAL BEING
 INSTALLED FOR THE RANGE AND THE TANKLESS WATER HEATER.
 WPB AMEND. TO FBC SEC. 107.2.1. 3RD REQUEST.
 PLEASE CALL THIS REVIEWER TO REVIEW THESE COMMENTS
 PRIOR TO RESUBMITTAL.
  