Plan Review Notes
Plan Review Notes For Permit 19040741
Permit Number 19040741
Review Stop G
Sequence Number 2
Notes
Date Text
2019-07-08 06:19:221) THERE ARE FOUR GAS RISER DIAGRAMS IN THIS SUBMITTAL
 PACKAGE AND I HAVE NO IDEA WHICH ONE IS TO BE USED. ALL
 DOCUMENTS NOT TO BE USED ARE TO BE REMOVED FROM THE
 SUBMITTAL PACKAGE AND TWO COMPLETE SETS OF PLANS ARE TO
 BE SUBMITTED FOR REVIEW AND APPROVAL. THIS SUBMITTAL IS
 DISORGANIZED AND CONFUSING AND A THOROUGH REVIEW COULD
 NOT BE PERFORMED.
 2) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. WPB
 AMEND. TO FBC SEC. 107.1.2ND REQUEST.
 3) SHOW THE SIZES AND TYPE OF PIPE MATERIAL BEING
 INSTALLED FOR THE RANGE AND THE TANKLESS WATER HEATER.
 WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
 4) THE GAS DRAWING REFERENCES A TABLE FOR CSST BUT
 THERE IS NO CSST SHOWN ON THE GAS DRAWING. CLARIFY. 2ND
 REQUEST.
  
 ***NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE AT
 THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  