2019-05-20 08:44:06 | GAS 2ND REVIEW**DENIED**FL ST 553.80 (B)2B WITH RESPECT |
| TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| 1) 2ND REQUEST. COPIES OF ANY SUBMITTAL DOCUMENTS THAT |
| IS SIGNED OR BEAR THE TITLE BLOCK OF A DESIGN |
| PROFESSIONAL MUST BE WET SIGNED. COPIES OF ANY |
| SUBMITTAL DOCUMENTS OF A P.E SIGNATURE IS NOT |
| PERMITTED. ANY FUTURE VIOLATION OF FAC 61G15-23.001 |
| WILL RESULT IN A COMPLAINT FILE WITH THE BOARD OF |
| PROFESSIONAL ENGINEERS. |
| |
| 2) HOLD DOWN DETAIL IS ILLEGIBLE. PROVIDE THE SIZE OF |
| THE HOLD-DOWN CABLES/STRAPS FOR THE TANK AND THE TYPE |
| AND LENGTH OF GROUND ANCHORS TO BE INSTALLED TO PREVENT |
| FLOTATION. NFPA 58 SEC. 6.6.1.6. |
| |
| 3) PROVIDE MANUFACTURES INSTALLATION MAUNAL FOR THE |
| TANK VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, |
| AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 GAS |
| APPLIANCES SHALL BE LISTED AND LABELED |
| |