2019-04-22 14:42:04GAS 1ST REVIEW**DENIED**
  
 1) COPIES THAT BARE THE SIGNATURE FOR P.E GORDON
 DIBATISTO SHALL BE WET SIGNED. FAC 61G15-23.001
  
 2) HOLD DOWN DETAIL IS ILLEGIBLE. PROVIDE THE SIZE OF
 THE HOLD-DOWN CABLES/STRAPS FOR THE TANK AND THE TYPE
 AND LENGTH OF GROUND ANCHORS TO BE INSTALLED TO PREVENT
 FLOTATION. NFPA 58 SEC. 6.6.1.6.
  
 3) PROVIDE MANUFACTURES INSTALLATION MAUNAL FOR THE
 TANK VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58,
 AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 GAS
 APPLIANCES SHALL BE LISTED AND LABELED
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR