Plan Review Notes
Plan Review Notes For Permit 19040663
Permit Number 19040663
Review Stop P
Sequence Number 4
Notes
Date Text
2019-07-11 14:46:04PROVISO PLANS REDLINED.
  
 1) EACH BUILDING DRAIN REQUIRES 1 VENT THAT EXTENDS TO
 THE OUTDOORS. THE DIPPING WELL, HAND SINK, AND THE ICE
 CUBE DRAIN ALL SHOW AAV VENTS. PROVIDE 1 THAT VENTS TO
 THE OUTDOORS ON THIS BUILDING DRAIN. FBC P 904.1. THE
 ONLY VENT THAT EXTENDS IS ON THE INLET SIDE OFT HE
 GREASE INTERCEPTOR.
  
 3) PROVIDE SHUT OFF VALVES AT THE TOP OF EVERY WATER
 DOWN FEED PIPE. FBC P 606.1 (5). ACCESS PANEL TO THESE
 VALVES SHALL BE PROVIDE. FBC P606.3
  
 4) PROVIDE BATHROOM ACCESSIBILITY DETAILS FOR THE GRAB
 BARS AND THE TOILET PAPER HOLDER. FBC-ACC 604.5.1,
 604.5.2, 604.7, 603.3, 604.2, 604.6, 604.4, 606.3,
 609.4
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  