2019-07-08 12:07:02PLUMBING 3RD REVIEW**DENIED**
  
 1) EACH BUILDING DRAIN REQUIRES 1 VENT THAT EXTENDS TO
 THE OUTDOORS. THE DIPPING WELL, HAND SINK, AND THE ICE
 CUBE DRAIN ALL SHOW AAV VENTS. PROVIDE 1 THAT VENTS TO
 THE OUTDOORS ON THIS BUILDING DRAIN. FBC P 904.1. THE
 ONLY VENT THAT EXTENDS IS ON THE INLET SIDE OFT HE
 GREASE INTERCEPTOR.
  
 2) SHT. P1 PLUMBING ISOMETRIC THE TOILET IS MISSING
 FROM THE DRAWING. FBC 107.3.5
  
 3) PROVIDE SHUT OFF VALVES AT THE TOP OF EVERY WATER
 DOWN FEED PIPE. FBC P 606.1 (5). ACCESS PANEL TO THESE
 VALVES SHALL BE PROVIDE. FBC P606.3
  
 4) PROVIDE BATHROOM ACCESSIBILITY DETAILS FOR THE GRAB
 BARS AND THE TOILET PAPER HOLDER. FBC-ACC 604.5.1,
 604.5.2, 604.7
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR