2019-06-12 09:19:17 | |
| 2ND REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. YOUR SIZING CALCULATION FOR YOUR GREASE INTERCEPTOR |
| IS INACCURATE THIS FORMULA IS MEANT TO BE USED FOR |
| LARGER SIT DOWN RESTAURANTS AND IT IS ONLY LISTING 1 |
| SEAT AND THE PLAN SHOWS 4, YOU NEED TO USE THE |
| CALCULATIONS THE USE THE VOLUME OF THE SINKS TO |
| DETERMINE THE GPM ALSO KNOWN AS THE PDI METHOD. IN |
| ORDER TO APPROVE THIS INTERCEPTOR YOU SHALL PROVIDE |
| SIZING CALCULATIONS FROM THE MANUFACTURE THEY CAN BE |
| EASILY FOUND ON THE MANUFACTURE,S WEB SITE. PER FBC PL |
| 1003.2 AND WPB AMEND TO FBC 107.2.1 |
| |
| 2. YOU PROVIDED MANUFACTURE SPECIFICATIONS BUT YOU DID |
| NOT LIST THE MODEL THAT YOU WILL BE USING PLEASE MARK |
| THE MODEL ON THE SPECS AND PROVIDE MANUFACTURE |
| INSTALLATION GUIDE. WPB AMEND TO FBC 107.2.1 |
| |
| 3. YOUR SANITARY ISOMETRIC IS NOTING STUDOR VENTS ON |
| ALL OF THE VENT STACKS AT LEAST ONE OF THE VENTS SHALL |
| DISCHARGE TO THE EXTERIOR OF THE BUILDING.PER FBC PL |
| 904.1 |
| |
| 4. THE ICE MACHINE REQUIRES A AIR HAMMER ARRESTOR |
| LOCATE AT THE APPLIANCE.PER FBC PL 604.9 |
| |
| 5. SHUT OFF VALVES ARE REQUIRED AT ALL DROPS ON THE HOT |
| AND COLD WATER SYSTEM PLEASE SHOW ON ISOMETRIC . PER |
| FBC PL 606.1(5) |
| |
| 6. PLEASE NOTE ON THE PLAN THE EXISTING FLOOR DRAIN |
| SHALL HAVE A TRAP PRIMER.FBC PL 1002.4.1 |
| |
| 7. THE 3 COMP SINK AND THE PREP SINK SHALL BE INDIRECT |
| WASTE PLEASE NOT ON PLAN. PER FBC PL 802.1.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |