Plan Review Notes For Permit 19040663 |
Permit Number |
19040663 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-05-23 15:30:56 | 5/23/19 | | | | IN A EFFORT TO MOVE THIS PROJECT FORWARD THE FOLLOWING | | WAS PROVIOSED | | | | | | 1) SHEET CVR - YOUR OCCUPANCY CLASSIFICATION WAS | | MODIFIED AND LOADS RECLACULATED PER THE FLORIDA FIRE | | PREVENTION CODE. | | | | USING A BUSINESS OCCUPANCY CALCULATION OF 10 FOR THIS | | ENTIRE SPACE IS AN INCORRECT APPLICATION OF THE CODE. | | | | THIS IS AN ASSEMBLY OCCUPANCY WITH LESS THAN 50 PERSON, | | AND THUSLY MERCANTILE PER THE FFPC. | | | | THE OCCUPANCY LOAD CALCULATION; HOWEVER, DOES NOT | | CHANGE FOR THE ASSEMBLY SPACE. | | | | YOU WERE GIVEN CREDIT FOR BUSINESS, KITCHEN AND STORAGE | | USE FORMULAS IN THOSE OTHER APPLICABLE AREAS . | | | | YOUR TOTAL OCCUPANCY LOAD IS 31. | | | | | | 2) SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE | | CONTACT MY OFFICE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|