Plan Review Notes
Plan Review Notes For Permit 19040663
Permit Number 19040663
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-05-23 15:30:565/23/19
  
 IN A EFFORT TO MOVE THIS PROJECT FORWARD THE FOLLOWING
 WAS PROVIOSED
  
  
 1) SHEET CVR - YOUR OCCUPANCY CLASSIFICATION WAS
 MODIFIED AND LOADS RECLACULATED PER THE FLORIDA FIRE
 PREVENTION CODE.
  
 USING A BUSINESS OCCUPANCY CALCULATION OF 10 FOR THIS
 ENTIRE SPACE IS AN INCORRECT APPLICATION OF THE CODE.
  
 THIS IS AN ASSEMBLY OCCUPANCY WITH LESS THAN 50 PERSON,
 AND THUSLY MERCANTILE PER THE FFPC.
  
 THE OCCUPANCY LOAD CALCULATION; HOWEVER, DOES NOT
 CHANGE FOR THE ASSEMBLY SPACE.
  
 YOU WERE GIVEN CREDIT FOR BUSINESS, KITCHEN AND STORAGE
 USE FORMULAS IN THOSE OTHER APPLICABLE AREAS .
  
 YOUR TOTAL OCCUPANCY LOAD IS 31.
  
  
 2) SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE
 CONTACT MY OFFICE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  