2019-05-31 11:10:43 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30 |
| 2. PROVIDE ACCURATE LOAD CALCULATION FOR COMMERCIAL |
| SERVICE INCLUDING ALL LOADS. NEC 220; WPB FBC 107.2.1 |
| 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 |
| 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| 105.1, 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |