Plan Review Notes
Plan Review Notes For Permit 19040663
Permit Number 19040663
Review Stop B
Sequence Number 2
Notes
Date Text
2019-06-10 09:57:48SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTE:
 PLANS THAT WERE REVIEWED THE FIRST TIME WERE NOT
 RE-SUBMITTED. THIS MAKES THE REVIEW MORE DIFFICULT
 BECAUSE THERE IS NO REFERENCE OF WHAT WAS REVIEWED. IN
 THE FUTURE PLEASE SUBMIT THE PLANS THAT WERE REVIEWED
 TO HELP EXPEDITE THE REVIEW PROCESS. THANK YOU.
  
  
  
 1) OK.
  
 ORIGINAL COMMENT:
 2) THE COVERSHEET UNDER THE HEADING OCCUPANCY LOADS
 STATES THE CUSTOMER AREA AS BASED ON STANDING
 UNCONCENTRATED TABLES AND CHAIRS @ 15 SQ. FT. PER
 OCCUPANT. PLEASE REVIEW THE 2017 FBC-B
 TABLE 1004.1.2.
 ASSEMBLY WITHOUT FIXED SEATS
 CONCENTRATED (CHAIRS ONLY- NOT FIXED 7 NET
 STANDING SPACE 5 NET
 UNCONCENTRATED (TABLES & CHAIRS) 15 NET
  
 YOU NEED TO DECIDE IF YOU ARE TAKING THE SQUARE FEET AT
 STANDING 441/5= 89 OCCUPANTS REQUIRING 2 EXITS.
 OR
 IF YOU ARE TAKING THE UNCONCENTRATED (TABLES & CHAIRS)
 @ 15 NET. 441/15=30 OCCUPANTS.
  
 RESPONSEE:
 REVISED CALCULATIONS SHOW 10 PEOPLE AS THE TOTAL NUMBER
 OF PEOPLE. THIS IS INCORRECT. THE OCCUPANT LOAD IS
 BASED ON THE ACTUAL FUNCTION OF EACH SPACE AS REQUIRED
 BY TABLE 1004.1.2 FBC-BUILDING. PROVIDE THE OCCUPANT
 LOAD OF EACH ROOM OR AREA AS REQUIRED BY SEC.
 1004.1.1.1 FBC-BUILDING, THEN ADD THEM UP AND PROVIDE
 THE TOTAL OCCUPANT LOAD.
 NOTE: THE BUSINESS CLASSIFICATION IS JUST FOR THE
 OCCUPANCY CLASSIFICATION SINCE THIS IS AN SMALL
 ASSEMBLY GROUP WITH AN OCCUPANT LOAD OF LESS THAN 50
 PEOPLE. OCCUPANT LOAD IS ALWAYS CALCULATED USING TABLE
 1004.1.2.
  
 ORIGINAL COMMENT:
 3) PLEASE NOTE ON THE COVER SHEET THE DESIGNER OF
 RECORD HAS THE NUMBER OF EXITS REQUIRED AS 1 BUT 2
 PROVIDED AND THE MAXIMUM TRAVEL DISTANCE OF 27 FEET 6
 INCHES. IF THE TRAVEL DISTANCE IS GOING TO BE TAKEN
 FROM THE MIDDLE OF THE FLOOR REQUIRING THE 2 EXITS,
 THEN SHOW COMPLIANCE WITH:
 2017 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION
 TO ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT
 LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY
 WITH 404.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 THERE IS AT LEAST A 6 INCH DROP OUT THE BACK DOOR TO
 THE COURTYARD DECK MAKING IT NOT ABLE TO BE AN
 ACCESSIBLE MEANS OF EGRESS.
  
 RESPONSE:
 A)THE MEASUREMENT OF THE TRAVEL DISTANCE IS TAKEN FROM
 THE MOST REMOTE POINT TO THE ENTRANCE TO AN EXIT. SEE
 SEC. 1017.3 FBC-BUILDING. LIFE SAFETY PLAN ON SHEET A-1
 SHOWS THE DISTANCE FROM THE REAR DOOR TO THE ENTRY
 DOOR. CLARIFY WHY MEASURING THE DISTANCE FROM ONE DOOR
 TO THE OTHER. IT LOOKS LIKE THE MOST REMOTE POINT WOULD
 BE THE FREEZER. REVISE AS REQUIRED.
  
 B) REVISE THE EGRESS WIDTH INFORMATION SHOWN ON SHEET
 CVR:
 (1)REVISE THE NUMBER OF OCCUPANTS. SEE RESPONSE TO
 COMMENT #2 ABOVE AND REVISE THE EGRESS WIDTH PROVIDED.
 36" PROVIDED IS INCORRECT. THE WIDTH PROVIDED IS THE
 CLEAR WIDTH OPENING NOT THE SIZE OF THE DOOR. SEE SEC.
 1010.1.1 FBC-BUILDING FOR PROPER WAY OF DIMENSIONING
 THE CLEAR WIDTH AND REVISE AS REQUIRED. TYPICALLY A 36"
 DOOR WOULD PROVIDE 32" CLEAR WIDTH OPENING. NOTE:
 PROVIDE THE SIZE OF THE EXISTING DOORS. DORO SCHEDULE
 DOESN'T SPECIFY THE SIZE OF THE EXISTING DOORS. THIS
 INFORMATION IS REQUIRED.
  
 (1)THERE IS NOT TABLE 1005.1 IN TH FBC-BUILDING CODE.
  
  
 4) OK. ARCHITECT'S RESPONSE LETTER STATES THAT " THE
 TENANT DOES NOT INTEND TO USE THE COURTYARD FOR
 SEASONAL SEATING".
  
 4A) OK.
  
 4B) OK.
  
 4C) OK.
  
 4D)OK.
  
 ORIGINAL COMMENT:
 4D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 RESPONSE:
 KNEE AND TOE CLEARANCES WERE NOT PROVIDED. THERE ARE NO
 DETAILS FOR FRONT COUNTER AND PICK UP COUNTER BY THE
 PREP/SERV AREA.
 ALSO, CLARIFY WHERE DOES RECEPTION COUNTER ADA DETAIL
 5/A-2 APPLIES TO?. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 4D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 RESPONS:
 THE HEIGHT OF THE PICK UP COUNTER DOESN'T COMPLY.
 REVISE AS REQUIRED.
 ALSO, CLARIFY WHERE DOES RECEPTION COUNTER ADA DETAIL
 5/A-2 APPLIES TO?. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 5) THE VALUE FOR THIS PERMIT IS EXTREMELY LOW
 CONSIDERING ALL OF THE KITCHEN EQUIPMENT THAT IS GOING
 INTO THIS SPACE AND THE REQUIRED GREASE TRAP. 109.3*
 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 RESPONSE:
 PLEASE PROVIDE THE ITEMIZED LIST REQUESTED BY THE
 PREVIOUS PLANS EXAMINER. INLCUDE THE DESIGN
 PROFESSIONAL FEES.
  
  
 ORIGINAL COMMENT:
 6) PLEASE PROVIDE THE DIMENSION OF THE EXISTING
 RESTROOM TO SEE IF THE RESTROOM COMPLIES WITH THE 2017
 FBC-ACCESSIBILITY CODE? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES THAT THE RESTROOM
 DESIGN HAS BEEN REVISED TO CONFORM TO THE 2017
 FBC-ACCESSIBILITY CODE".
 FLOOR PLANS WERE REVISED BUT IS NOT CLEAR WHAT WALLS
 ARE NEW AND WHAT WALLS ARE EXISTING. PLEASE COORDINATE
 WITH THE WALL PLAN LEGEND AND REVISE ACCORDINGLY TO
 AVOID CONFUSION. SEC. 107.2.1 CITY AMENDMENTS.
  
  
 7) OK.
  
 ORIGINAL COMMENT:
 8) SHEET A-1 SHOWS UNDER THE STAIR STORAGE. PLEASE SHOW
 HOW COMPLIANCE WITH THE 2017 FBC-B SECTION
 1011.7.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. THE WALLS
 AND SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER
 ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION OR THE
 FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER.
  
 RESPONSE:
 DETAIL PROVIDED ON SHEET A-1 DOESN'T SEEM TO APPLY TO
 THE EXISTING CONDITIONS. PROVIDE DETAIL THAT MATCHES
 EXISTING CONDITIONS. SEC. 107.2.1 CITY AMENDMENTS.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. SUBMIT OLD DRAWINGS FOR REFERENCE. (PLEASE
 DON'T STAPLE OLD DRAWINGS TO RESUBMITTED PACKAGE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 10- A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED
 AFTER COMPLETION OF WORK.
 SEC. 1001.2 FBC-EXISTING BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  