Date |
Text |
2019-04-25 12:12:26 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE PREVIOUS OCCUPANCY OF THE THIS SPACE WAS A |
| MERCANTILE WHICH WOULD MAKE THIS A CHANGE OF OCCUPANCY |
| NOT LEVEL 2 ALTERATION. PER BUSINESS LICENSE RECORD OF |
| PROPERTY. SHALL COMPLY WITH FBC EX 506.1 AND CH 10 |
| |
| 2. THE COVER SHEET STATES AS BUSINESS OCCUPANCY SHT A-1 |
| UNDER LIFE SAFETY NOTES LIST IT AS MERCANTILE PLEASE |
| CLARIFY. THIS IS AN ASSEMBLY THAT IS CLASSIFIED AS A |
| BUSINESS PER FBC 303.1.1 SMALL BUILDINGS AND TENANT |
| SPACES. A BUILDING OR TENANT SPACE USED FOR ASSEMBLY |
| PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS |
| SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY. |
| |
| 3. TWO BATHROOMS ARE REQUIRED PER FBC PL 403.2 SEPARATE |
| FACILITIES. WHERE PLUMBING FIXTURES ARE REQUIRED, |
| SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX. PER |
| FBC EX 1010.1 |
| |
| 4. IS THE EXISTING BATHROOM FULLY ACCESSIBLE PER 2017 |
| FBC ACC 6TH EDITION PLEASE SHOW LEVEL OF ACCESSIBILITY |
| SUCH AS GRAB BARS TOILET AND LAVATORY AND CLEAR FLOOR |
| SPACE FOR THE FIXTURES. PER WPB AMEND TO FBC 107.2.1. A |
| MINIMUM OF 20% OF THE TOTAL COST OF THE JOB SHALL BE |
| USED TO BRING UP THE LEVEL OF ACCESSIBILITY OF THE |
| SPACE. PER FBC ACC 202.4, 202.4.1 |
| |
| 5.EVEN THOUGH THERE MAY NOT BE COCKING BEING DONE ANY |
| TIME FOOD OR DRINKS ARE BEING MADE THAT COULD PRODUCE |
| ANY TYPE OF GREASE SUCH AS DIARY , NUT BUTTERS A GREASE |
| TRAP IS REQUIRED FOR ANY TYPE OF KITCHEN THERE ARE NO |
| EXEMPTIONS. PER FBC PL 1003.1 AND WPB UTILITIES |
| DEPARTMENT FOG PROGRAM |
| |
| 6. PLEASE PROVIDE A WATER ISOMETRIC DRAWING. PER FBC PL |
| 107.3.5.1.3 |
| |
| 7. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC 416.5 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |