Plan Review Notes
Plan Review Notes For Permit 19040655
Permit Number 19040655
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-04-26 11:01:18PERMIT # 19040655
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND
 IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER
 LOCK FOR DEDICATED BRANCH CIRCUIT.
  
 2) COMPLIANCE WITH NFPA 72 REQUIREMENTS FOR DEVICE
 PLACEMENT ENSURING THAT ALL AUDITORY AND VISUAL
 REQUIREMENTS ARE MET, WILL BE VERIFIED IN THE FIELD
 DURING THE FIRE ALARM TEST INSPECTION.
 PLACEMENT OF ADDITIONAL DEVICES MAY BE REQUIRED IF IT
 IS DETERMINED THAT THERE IS A DEFICIENCY IN COMPLIANCE.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  