Plan Review Notes
Plan Review Notes For Permit 19040635
Permit Number 19040635
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-25 09:23:54PLUMBING 1ST REVISION**DENIED**
  
 1) SHT. A2 PROVIDE TURNING SPACE FOR BOTH THE WAITING
 ROOM ACCESSABLE AND WOMENS ACCESSABLE TOILET ROOMS.
 FBC-ACC 603.2.1
  
 2) SHT.A2 WOMENS ACCESSABLE TOILET ROOM SHOWS THE DOOR
 SWING INTO THE CLEAR FLOOR SPACE. FBC-ACC 603.2.3. SHOW
 COMPLIANCE EXCEPTIONS AS CALLED OUT IN FBC-ACC 305.3
  
 3) SHT. A2 PROVIDE CLEAR FLOOR SPACE FOR THE DRINKING
 FOUNTAIN. FBC-ACC 602.2
  
 4) EXAM ROOM #4 IS SHOWN AS ACCESSABLE. SHOW CLEAR
 FLOOR SPACE AND APPROACH AND COUNTER TOP AS BEING MAX
 34". FBC-ACC 606.2, 606.3, 606.3
  
 5) SHT. P5.2 WATER PIPING ISOMETRIC IS STILL SHOWING
 LAV SINK THAT WAS REMOVEDIN PLACE OF CHANGING STATION.
 FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  