2019-04-11 11:05:51 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| |
| NOTE: |
| PLAN REVIEW FEES WERE NOT PAID. |
| FUTURE REVIEWS WILL NOT BE PERFORMED UNTIL FEES ARE |
| PAID. |
| |
| |
| 1- ROOF TILE FLORIDA PRODUCT APPROVAL FL7473-R8 |
| SUBMITTED. : CLEARLY SPECIFY ROOF TILE FASTENING METHOD |
| AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS: |
| (A) FOR MECHANICALLY ATTACHED TILE PROVIDE COMPLETE |
| TILE FASTENING INFORMATION AS REQUIRED BY SEC. 6.3.1 OF |
| FLORIDA PRODUCT APPROVAL SUBMITTED. CLEARLY SPECIFY |
| NUMBER OF SCREWS/NAILS AND SIZE TO BE INSTALLED PER |
| TILE. |
| |
| (B) FOR ADHESIVE-SET TILE PROVIDE COMPLETE INFORMATION |
| AS REQUIRED BY SEC. 6.3.3 OF FLORIDA PRODUCT APPROVAL |
| SUBMITTED. AND, CLEARLY SPECIFY PADDY SIZE. |
| |
| (C) FOR MORTAR-SET TILE PROVIDE COMPLETE INFORMATION AS |
| REQUIRED BY SEC. 6.3.2 OF FLORIDA PRODUCT APPROVAL |
| SUBMITTED. AND, CLEARLY SPECIFY PADDY SIZE. |
| |
| 2- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL |
| FL5259-R28 SUBMITTED. FOR ADHESIVE OR MORTAR ROOF TILE |
| INSTALLATION CLEARLY SPECIFY WHICH UNDERLAYMENT SYSTEM |
| FROM SEC. 5.6.4 OF PRODUCT APPROVAL SUBMITTED IS GOING |
| TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL FOR ALL ROOF |
| ZONES. |
| |
| 3- CONTRACTOR NEEDS TO SPECIFY ON THE PERMIT |
| APPLICATION THE ROOF AREA, ROOF PITCH AND MEAN ROOF |
| HEIGHT AS REQUIRED BY CITY POLICY FOR ALL ROOFING |
| PERMITS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |