Plan Review Notes For Permit 19040534 |
Permit Number |
19040534 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-04-10 19:16:29 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- FLAT ROOF: PROVIDE PRODUCT APPROVAL (2 COPIES) AS | | REQUIRED BY FAC 61G20-3.001 . AND, CLEARLY MARK WHICH | | APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1 | | FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T | | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN | | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. | | | | 2- PROVIDE SHINGLES COMPLETE FLORIDA PRODUCT APPROVAL. | | PRODUCT APPROVAL SUBMITTED IS MISSING THE FLORIDA | | PRODUCT APPROVAL COVER PAGE. THIS PAGE IS REQUIRED | | BECAUSE IT SHOWS THE CURRENT CODE VERSION AND THE | | PRODUCT APPROVAL STATUS. CHAPTER 553 F.S. AND FAC | | 61G20-3.001. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|