2019-04-10 14:40:50BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLEASE PROVIDE PROOF OF COMPLIANCE WHERE ROOF
 DIAPHRAGMS, CONNECTIONS OF THE ROOF DIAPHRAGM TO ROOF
 FRAMING MEMBERS, AND ROOF-TO-WALL CONNECTIONS SHALL BE
 EVALUATED FOR THE WIND LOADS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING, INCLUDING WIND UPLIFT. FBC
 EXISTING FBC 1205.1; FBC EXISTING 707.3.2
  
 1205.1 STRICT COMPLIANCE.
  
 HISTORIC STRUCTURES OR PORTIONS OF SUCH STRUCTURES THAT
 DO NOT STRICTLY COMPLY WITH THIS CODE SHALL BE
 CONSIDERED TO BE IN COMPLIANCE IF IT CAN BE SHOWN TO
 THE SATISFACTION OF THE BUILDING CODE OFFICIAL THAT
 EQUIVALENT PROTECTION HAS BEEN PROVIDED OR THAT NO
 HAZARD WILL BE CREATED OR CONTINUED THROUGH
 NONCOMPLIANCE.
  
  
 [BS] 707.3.2 ROOF DIAPHRAGMS RESISTING WIND LOADS IN
 HIGH-WIND REGIONS.
  
 WHERE ROOFING MATERIALS ARE REMOVED FROM MORE THAN 50
 PERCENT OF THE ROOF DIAPHRAGM OR SECTION OF A BUILDING
 LOCATED WHERE THE ULTIMATE DESIGN WIND SPEED, VULT,
 DETERMINED IN ACCORDANCE WITH FIGURE 1609.3(1) OF THE
 FLORIDA BUILDING CODE, BUILDING, IS GREATER THAN 115
 MPH (51 M/S), AS DEFINED IN SECTION 1609 (THE
 HIGH-VELOCITY HURRICANE ZONE SHALL COMPLY WITH SECTION
 1620) OF THE FLORIDA BUILDING CODE, BUILDING, ROOF
 DIAPHRAGMS, CONNECTIONS OF THE ROOF DIAPHRAGM TO ROOF
 FRAMING MEMBERS, AND ROOF-TO-WALL CONNECTIONS SHALL BE
 EVALUATED FOR THE WIND LOADS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING, INCLUDING WIND UPLIFT. IF THE
 DIAPHRAGMS AND CONNECTIONS IN THEIR CURRENT CONDITION
 ARE NOT CAPABLE OF RESISTING AT LEAST 75 PERCENT OF
 THOSE WIND LOADS, THEY SHALL BE REPLACED OR
 STRENGTHENED IN ACCORDANCE WITH THE LOADS SPECIFIED IN
 THE FLORIDA BUILDING CODE, BUILDING.
  
 EXCEPTIONS:
  
 1.THIS SECTION DOES NOT APPLY TO BUILDINGS PERMITTED
 SUBJECT TO THE FLORIDA BUILDING CODE.
 2.THIS SECTION DOES NOT APPLY TO BUILDINGS PERMITTED
 SUBJECT TO THE 1991 STANDARD BUILDING CODE, OR LATER
 EDITION, OR DESIGNED TO THE WIND LOADING REQUIREMENTS
 OF THE ASCE 7-88 OR LATER EDITIONS, WHERE AN EVALUATION
 IS PERFORMED BY A REGISTERED DESIGN PROFESSIONAL TO
 CONFIRM THE ROOF DIAPHRAGM, CONNECTIONS OF THE ROOF
 DIAPHRAGM TO ROOF FRAMING MEMBERS, AND ROOF-TO-WALL
 CONNECTIONS ARE IN COMPLIANCE WITH THE WIND LOADING
 REQUIREMENTS OF EITHER OF THESE STANDARDS OR LATER
 EDITIONS.
 3.BUILDINGS WITH STEEL OR CONCRETE MOMENT RESISTING
 FRAMES SHALL ONLY BE REQUIRED TO HAVE THE ROOF
 DIAPHRAGM PANELS AND DIAPHRAGM CONNECTIONS TO FRAMING
 MEMBERS EVALUATED FOR WIND UPLIFT.
 4. THIS SECTION DOES NOT APPLY TO SITE-BUILT
 SINGLEFAMILY DWELLINGS. SITE-BUILT SINGLE-FAMILY
 DWELLINGS SHALL COMPLY WITH SECTIONS 706.7 AND 706.8.
 5.THIS SECTION DOES NOT APPLY TO BUILDINGS PERMITTED
 WITHIN THE HVHZ AFTER JANUARY 1, 1994 SUBJECT TO THE
 1994 SOUTH FLORIDA BUILDING CODE, OR LATER EDITIONS, OR
 WHERE THE BUILDING?S WIND DESIGN IS BASED ON THE WIND
 LOADING REQUIREMENTS OF ASCE 7-88 OR LATER EDITIONS.