2019-07-02 14:56:47 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| PAGE E-1 RECEPTACLE NEEDS TO BE INSTALLED AT FRONT OF |
| BUILDING |
| E3901.7 OUTDOOR OUTLETS. |
| NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| INSTALLED OUTDOORS AT THE |
| FRONT AND BACK OF EACH DWELLING UNIT HAVING DIRECT |
| ACCESS TO GRADE LEVEL. BALCONIES, DECKS, AND PORCHES |
| THAT ARE ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT |
| SHALL HAVE AT LEAST ONE |
| RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE |
| BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE |
| LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE |
| THE BALCONY, DECK, |
| OR PORCH SURFACE. |
| |
| KITCHEN COUNTER LOOKS TO BE MISSING OUTLETS FOR SPACING |
| E3901.4 COUNTERTOP RECEPTACLES. |
| IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND |
| SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR |
| COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH |
| SECTIONS E3901.4.1 THROUGH E3901.4.5 |
| |
| OUTLETS INSTALLED SHALL MEET E3902 OF FBC FOR GFCI AND |
| AFCI PROTECTION. |
| |
| R315.1CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN |
| ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT |
| THAT EMITS CARBON MONOXIDE AS BYPRODUCT OF COMBUSTION |
| SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM |
| INSTALLED WITHIN |
| 10 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. |