Plan Review Notes
Plan Review Notes For Permit 19040469
Permit Number 19040469
Review Stop B
Sequence Number 3
Notes
Date Text
2019-07-09 16:58:20NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 ORIGINAL COMMENT:
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE).
 SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN).
 SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION).
 NOTE: THERE IS NO MUCH ROOM ON THE REAR OF THE LOT.
 CLEARLY SHOW HOW RETAINING THE WATER IN THE REAR OF THE
 LOT WITHOUT DUMPING INTO THE NEIGHBOR'S PROPERTY.
  
 RESPONSE:
 SURVEY WAS REVISED AGAIN. NOW IT SHOWS A "DRY RETENTION
 AREA" ON THE FRONT OF THE LOT. A RETENTION AREA IS NOT
 REQUIRED ON THE FRONT OF THE LOT AND THIS IS NOT WHAT
 IT WAS REQUESTED ON MY PREVIOUS COMMENT. THE PREVIOUS
 SURVEY SHOWED A DRAINAGE FLOW DIRECTION ARROW GOING
 TOWARDS THE STREET. THIS WAS OK. THE RETENTION AREA IS
 NOT REQUIRED ON THE FRONT OF THE LOT, BUT IF CONTRACTOR
 WANTS TO BUILD A RETENTION AREA IS OK. THE CONCERN WAS
 ON THE REAR OF THE PROPERTY. NEED TO KEEP THE WATER
 WITHIN THE LOT AND NOT DRAINING TOWARDS THE NEIGHBOR'S
 PROPERTIES. THAT IS WHY THE PROPOSED BERM ON THE REAR
 OF THE PROPERTY WAS NOT ALLOWED. REVISE AS REQUIRED.
  
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) OK.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. NAME OF PERSON DOING THE
 CALCULATIONS WAS NOT PROVIDED. ONLY THE SIGNATURE WAS
 PROVIDED.
  
 D) OK.
  
 ORIGINAL COMMENT:
 E)WINDOW AREA SHOWN ON PAGE 3 OF 4 DOESN'T MATCH
 INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 WINDOW AREA IS CORRECT NOW BUT THE BUILDING ORIENTATION
 WAS CHANGED. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: TYPICALLY PLANS ARE SHOWN WITH NORTH ARROW FACING
 UP. PLANS SUBMITTED SHOW NORTH ARROW FACING DOWN. KEEP
 THIS IN CONSIDERATION WHEN REVISING THE ENERGY
 CALCULATIONS.
  
 F) OK.
  
 NEW COMMENTS:
 G) NEW ENERGY CALCULATIONS SHOW ONLY ONE BEDROOM ON
 ITEM #4 OF PAGE 1 OF 5. THIS IS INCORRECT. SEE PLANS
 AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 H) REVISE DOORS INFORMATION ON SHEET 3 OF 5 TO MATCH
 PLANS AND PRODUCT APPROVALS. REVISE ORIENTATION OF
 DOORS. COORDINATE WITH ITEM #2(E) ABOVE. AND SEE
 PRODUCT APPROVALS FOR DOORS. EXTERIOR DOORS ARE NOT
 WOOD. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I) CLARIFY SPACES INFORMATION SHOWN ON PAGE 2 OF 5. WHY
 CALCULATING FOUR OCCUPANTS ON ONE BEDROOM HOUSE?.
 COORDINATE WITH ITEM #2(G) ABOVE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  