Plan Review Notes
Plan Review Notes For Permit 19040469
Permit Number 19040469
Review Stop B
Sequence Number 2
Notes
Date Text
2019-06-26 13:08:58NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE).
 SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN).
 SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION).
 NOTE: THERE IS NO MUCH ROOM ON THE REAR OF THE LOT.
 CLEARLY SHOW HOW RETAINING THE WATER IN THE REAR OF THE
 LOT WITHOUT DUMPING INTO THE NEIGHBOR'S PROPERTY.
  
 RESPONSE:
 SURVEY WAS REVISED. BUT IT DOESN'T PROVIDE
 SPECIFICATIONS OF HOW TO KEEP THE WATER WITHIN THIS
 LOT. BASED ON THE GRADE ELEVATION SHOWN, IT LOOKS LIKE
 THE INTENTION IS TO CREATE A BERM ON THE REAR OF THE
 PROPERTY. THIS IS NOT ACCEPTABLE. NEED TO KEEP THE
 WATER WITHIN THE LOT. A BERM WILL DIRECT WATER TO THE
 ADJACENT PROPERTIES. NEED TO KEEP THE WATER WITHIN THE
 SITE. REVISE AS REQUIRED.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) OK.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NAME OF PERSON DOING THE CALCULATIONS
 WAS NOT PROVIDED.
  
 ORIGINAL COMMENT:
 D) ACCORDING TO PROJECT INFORMATION ON TOP OF PAGE 2 OF
 4, THE HOUSE WAS ROTATED 180 DEGREES. CLARIFY WHY ITEM
 #5 ON PAGE 1 OF 4 STATES THAT THIS IS NOT A WORST CASE
 SCENARIO AND THEN THE HOUSE IS ROTATED 180 DEGREES?.
 CALCULATIONS NEED TO BE DONE FOR THE ACTUAL ORIENTATION
 OF THE HOUSE AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION. REVISE CALCULATIONS AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. CALCULATIONS WERE NOT
 REVISED.
  
 ORIGINAL COMMENT:
 E)WINDOW AREA SHOWN ON PAGE 3 OF 4 DOESN'T MATCH
 INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. CALCULATIONS WERE NOT
 REVISED.
  
 ORIGINAL COMMENT:
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. CALCULATIONS WERE NOT
 REVISED.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  