2019-11-08 16:55:11NEW AUTOMOBILE DEALERSHIP, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTICE: *************** 4X FEE / NOTICE!!!!!
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B) ******************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) SHEET 002-G-101 THE LIFE SAFETY PLAN:
  
 ORIGINAL COMMENT:
 1A) 3RD REQUEST. UNDER THE HEADING BUILDING CODE
 SUMMARY THE PROPOSED USE IS LISTED AS BUSINESS (B) AND
 STORAGE (S1). PLEASE NOTE THAT THE SERVICE SHOP IS
 LISTED AS A S1 OCCUPANCY. FOR MOTOR VEHICLE REPAIR
 GARAGES COMPLYING WITH THE MAXIMUM ALLOWABLE QUANTITIES
 OF HAZARDOUS MATERIALS LISTED IN TABLE 307.1(1).
 PLEASE SUBMIT A LIST OF HAZARDOUS MATERIALS AND
 ALLOWABLE QUANTITIES PER THE 2017 FBC-B TABLE 307.1(1).
  
 RESPONSE:
 THE SAME RESPONSE THAT WAS PROVIDED ON THE PREVIOUS
 COMMENT WAS PROVIDED THIS TIME AGAIN. THE ONLY
 DIFFERENCE IS THAT THE NOTE "G-101 NOTE ADDED (CLOUD
 3)" WAS ADDED.
 THIS DOESN'T ANSWER THE REQUEST FROM THE PREVIOUS
 REVIEWER. THE REQUEST IS TO PROVIDE THE LIST AND
 QUANTITIES OF EACH HAZARDOUS MATERIALS THAT ARE GOING
 TO BE STORED IN THIS PLACE. ALSO, CLEARLY SHOW ON PLANS
 LOCATION OF EACH MATERIAL. ARCHITECT MAY WANT TO
 COORDINATE THIS INFORMATION WITH THE OWNER OF THE
 DEALERSHIP TO VERIFY QUANTITIES OF EACH MATERIAL TO BE
 STORED IN THIS PLACE AND PROVIDE INFORMATION ON
 DRAWINGS.
  
  
 1B) OK
  
 ORIGINAL COMMENT:
 1C) SEMI-COMPLIED. UNDER THE BUILDING DATA THERE IS NO
 LISTING FOR THE REQUIRED AREA OF REFUGE, THIS IS A 2
 STORY BUILDING AND NO FIRE SPRINKLERS. THE 2017
 FBC-ACCESSIBILITY CODE UNDER SECTION 207 ACCESSIBLE
 MEANS OF EGRESS. SECTION 207.1. MEANS OF EGRESS SHALL
 COMPLY WITH SECTION 1007 OF THE INTERNATIONAL BUILDING
 CODE (2003 EDITION).
 PLEASE REVIEW IN THE 2003 IBC-B SECTIONS DEALING WITH:
  
 1007.3 ENCLOSED EXIT STAIRWAYS, 48 INCHES BETWEEN
 HANDRAILS.
 RESPONSE:
 OK. DIMENSIONS ON PLANS WERE REVISED, BUT INFORMATION
 ON SHEET G101 WAS NOT REVISED. REVISE AS REQUIRED TO
 MATCH.
  
 1007.4 ELEVATORS.
 RESPONSE:
 OK. NO USED AS MEANS OF EGRESS.
  
 1007.6 AREAS OF REFUGE.
 RESPONSE:
 OK. BUT, CLEARLY IDENTITY ON PLANS "AREA OF REFUGE AND
 SPECIFY SIZE.
  
 1007.6.1. SIZE.
 RESPONSE:
 CLEARLY IDENTITY ON PLANS "AREA OF REFUGE AND SPECIFY
 SIZE.
  
 1007.6.2. SEPARATION.
 RESPONSE:
 OK. NO REQUIRED.
  
 1007.6.3. TWO-WAY COMMUNICATION.
 RESPONSE:
 OK. BUT NEED TO CLEARLY SPECIFY IT ON PLANS. AND, TWO
 WAY COMMUNICATIONS SHALL INCLUDE BOTH AUDIBLE AND
 VISIBLE SIGNALS.
  
 1007.6.4. INSTRUCTIONS.
 RESPONSE:
 CLEARLY SPECIFY ON PLANS REQUIRED INSTRUCTIONS.
  
 1007.6.5. IDENTIFICATION.
 RESPONSE:
 CLEARLY PROVIDE ON PLANS THE IDENTIFICATION
 INFORMATION.
  
 1007.7.7. SIGNAGE.
 RESPONSE:
 CLEARLY SPECIFY ON PLANS SIGNAGE THAT ELEVATOR IS NOT
 AN APPROVED ACCESSIBLE MEANS OF EGRESS AND INDICATE
 LOCATION OF ACCESSIBLE MEANS OF EGRESS.
  
  
 ORIGINAL COMMENT:
 1D) 3RD REQUEST. SEPARATED MIXED OCCUPANCY SHOWS THE
 FORMULA FOR AREA CALCULATIONS BUT HAS LEFT THE
 CALCULATION BLANK. PLEASE PROVIDE THE ACTUAL AND
 ALLOWABLE SQUARE FEET FOR EACH OF THE OCCUPANCIES AND
 THE END CALCULATION. 2017 FBC-B 508.3.3.
  
 RESPONSE:
 OCCUPANCIES LISTED ON SHEET G-101 (A AND M OCCUPANCIES)
 DON'T CORRESPOND TO THE OCCUPANCIES LISTED UNDER
 "ALLOWABLE AREA" (B AND S-1 OCCUPANCIES). REVISE AS
 REQUIRED.
  
  
 ORIGINAL COMMENT:
 1E) SEMI-COMPLIED. PLEASE NOTE THE PLANS DOES NOT STATE
 THE ACTUAL OCCUPANT LOAD FOR EACH OF THE OCCUPANCIES.
 THE EXIT WIDTH DOES PROVIDE THE AREA FOR EACH OCCUPANCY
 AND AREA PER OCCUPANT (TABLE 1004.1.2) BUT DOES NOT
 GIVE THE ACTUAL OCCUPANT LOAD PER STORY AND THE TOTAL
 OCCUPANT LOAD. 2017 FBC-B 1004.1 & TABLE 1004.1.2.
  
 RESPONSE:
 INFORMATION SHOWN ON THE "EGRESS WIDTH" TABLE AND
 INFORMATION SHOWN ON PLANS DON'T MATCH. PROVIDE THE
 NUMBER OF PEOPLE FOR EACH OCCUPANCY BASED ON THE GROSS
 SQUARE FOOTAGE AS REQUIRED BY TABLE 1004.1.2
 FBC-BUILDING. AND, COORDINATE WITH NUMBER OF PEOPLE
 SHOWN ON FLOOR PLANS FOR EACH OCCUPANCY. CLARIFY WHY ON
 THE SECOND FLOOR THERE ARE MORE CHAIRS THAN NUMBER OF
 PEOPLE SPECIFIED?. SEC. 107.2.1 CITY AMENDMENTS.
  
 ALSO, REVISE INFORMATION ON THE EXIT WIDTH TABLE.
 REVISE SIZE OF STAIRS TO MATCH PLANS REVISED TO COMPLY
 WITH THE ACCESSIBILITY REQUIREMENTS. AND, REVISE THE
 "EGRESS CAPACITY FACTOR" OF THE STAIRS TO COMPLY WITH
 SEC. 1005.3.1 FBC-BUILDING. THE FACTOR IS 0.3 NOT 0.2.
  
 IN ADDITION, REVISE THE ACTUAL WIDTH OF OPENINGS FOR
 "OTHER EGRESS COMPONENTS" ( EGRESS DOORS FOR EXAMPLE).
 SEE SEC. 1010.1.1 FBC-BUILDING FOR ACTUAL SIZE OF
 EGRESS DOORS AND REVISE INFORMATION ON PLANS AS
 REQUIRED.
  
  
 ORIGINAL COMMENT:
 1F)KEY NOTES ON SHEET 041-A-101 INDICATE THE DESIGNER
 OF RECORD REQUIRING A 2 HOUR WALL BETWEEN THE B & S1
 OCCUPANCY AND DECLARING THE BLOCK TO COMPLY WITH
 (U905). THIS DESIGN REQUIRES A D-2 A 8 INCH BLOCK, AND
 2 HOUR FIRE RATED CONCRETE BLOCK. PLEASE NOTE WE WILL
 REQUIRE DOCUMENTATION FROM THE BLOCK MANUFACTURER THAT
 THEIR 2 HOUR RATING OF BLOCK COMPLIES WITH TABLE
 722.3.2. (2017 FBC-B) MINIMUM EQUIVALENT THICKNESS OF
 BEARING OR NONBEARING CONCRETE MASONRY WALLS. PROVIDE
 THE TYPE OF AGGREGATE AND EQUIVALENT THICKNESS FOR THE
 2 HOUR FIRE RATING. THE SAME FOR 12 INCH WIDE BLOCK,
 PROVIDE A LETTER FROM THE BLOCK MANUFACTURER.
  
 RESPONSE:
 WALL TYPES AND PLANS ARE NOT CLEAR. MISSING DETAILS FOR
 THE SPECIFIED FIRE RATED WALLS. PROVIDE COMPLETE WALL
 DETAIL FOR THE 2 HOUR FIRE RATED CONCRETE BLOCK WALLS
 (U905) SPECIFYING 2HR BLOCK. ALSO, PROVIDE COMPLETE
 WALL DETAIL FOR THE ONE HOUR FIRE RATED PARTITION
 (U419). AND, CLEARLY TAG THEM ON THE FLOOR PLANS. IN
 ADDITION, CLEARLY SPECIFY IF IT'S 8" OR 12" CONCRETE
 BLOCK. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1G) 3RD REQUEST. SHEET A-501 WALL TYPES A3-A6 ALL SHOW
 BLOCK WALLS WITH EITHER 8 INCH OR 12 INCH CMU. EACH
 DETAIL SHOULD BE SPECIFIC TO BLOCK TYPE AND WALL TYPE.
 AGAIN THESE DETAILS DO NOT MATCH THE WALL
 IDENTIFICATION TAGS LOCATED IN SHEETS 041-A-101 AND
 042-A-102. INFORMATION ON THE PLANS HAS TO BE SPECIFIC
 NO EITHER, OR. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 RESPONSE:
 SEE RESPONSE FOR ITEM 1(F) ABOVE.
  
 1H) OK.
  
  
  
 ORIGINAL COMMENT:
 SECOND ROUND OF COMMENTS. THE LIFE SAFETY SHEET
 002-G-101 SHOWS A SECOND STORY BUSINESS AND STORAGE
 OCCUPANCY, (ASSUMED S-1). THE TRAVEL DISTANCE IS SHOWN
 GOING DOWN THROUGH THE STAIRWAY MAKING THIS STAIRWAY
 EXIT ACCESS AND THE TRAVEL DISTANCE ON THE STAIRS TO BE
 TAKEN PARALLEL TO THE STAIRS. FROM THE FURTHEST POINT
 TAKEN ON THE SECOND FLOOR TO THE FIRST FLOOR LANDING
 THE TRAVEL DISTANCE IS BETWEEN 85 TO 90 FEET. THIS IS
 OVER THE ALLOWABLE MAXIMUM COMMON PATH OF TRAVEL FROM
 TABLE 1006.3.2(2) OF 75 FEET AND OCCUPANT LOAD OF 49
 FOR BUSINESS OR 29 FOR STORAGE OCCUPANCY. IF THE
 STAIRWAY WAS A RATED 1 HOUR EXIT STAIRWAY WITH OPENING
 PROTECTIVES AND EXIT PASSAGEWAY TO THE EXTERIOR, THEN
 THE TRAVEL DISTANCE FOR THE 2ND FLOOR WOULD WORK.
 PLEASE REVIEW ALL OF THE REQUIREMENTS FOR EXIT AND EXIT
 PASSAGEWAYS. EXIT PASSAGEWAYS ARE FOUND UNDER FBC-B
 1024. PLEASE REVIEW VENTILATION REQUIREMENTS (FBC-B
 1024.7) FOR EXIT PASSAGEWAYS AS WELL.
  
 RESPONSE:
 THIS IS A TWO STORY BUILDING. TABLE 1006.3.2(2)
 FBC-BUILDING IS THE TABLE THAT APPLIES TO THIS
 BUILDING. IF THERE IS A DIFFERENCE BETWEEN THE FIRE
 CODE AND BUILDING CODE THEN THE MOST STRINGENT CODE
 PREVAILS. IT LOOKS LIKE THE STAIRWAY IS GOING TO BE AT
 LEAST ONE HOUR FIRE RATED. REVISE TRAVEL DISTANCE. SHOW
 TRAVEL DISTANCE UP TO THE ENTRY OF THE STAIRWAY.
  
  
 ORIGINAL COMMENT:
 1J) 3RD REQUEST. VERSION # 2 STILL DOES NOT SHOW
 COMPLIANCE WITH FBC-B 1015.4 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW
 PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM
 THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT. ALSO
 THERE IS A DETAIL FOR RISE AND RUN BUT NO DIMENSION FOR
 COMPLIANCE WITH 1015.4 FBC-B EXCEPTION 2. THE
 TRIANGULAR OPENINGS AT THE OPEN SIDES OF A STAIR,
 FORMED BY THE RISER, TREAD AND BOTTOM RAIL SHALL NOT
 ALLOW PASSAGE OF A SPHERE 6 INCHES IN DIAMETER.
 1 ST ROUND OF COMMENTS. STAIRWAY GUARDRAIL. SHEET
 049-A-101. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE
 WITH: 2017 FBC-B 1015.4 OPENING LIMITATIONS. REQUIRED
 GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW PASSAGE OF A
 SPHERE 4 INCHES (102 MM) IN DIAMETER FROM THE WALKING
 SURFACE TO THE REQUIRED GUARD HEIGHT.
  
 RESPONSE:
 STAIR SECTION A4 ON SHEET 049-A-401 SPECIFIES 4"
 BETWEEN THE HORIZONTAL RAILING. THE DIMENSION NEEDS TO
 BE SMALLER THAN 4 INCHES SO IT DOESN'T ALLOW THE
 PASSAGE OF 4" SPHERE. REVISE AS REQUIRED.
 ALSO, THE REQUESTED INFORMATION FOR THE LIMITATIONS ON
 THE TRIANGULAR AREA AT THE OPEN SIDE OF THE STAIRS WAS
 NOT PROVIDED. PROVIDE COMPLETE INFORMATION.
  
  
 ORIGINAL COMMENT:
 2A) 3RD REQUEST. THERE MUST BE A PERMANENT MEANS OF
 EGRESS TO REACH THE ROOF TOP HATCH.
 1ST ROUND OF COMMENTS. SHEET 042-A102 THE 2ND FLOOR
 PLAN AND ROOF PLAN OF THE REPAIR GARAGE, SHOWS A ROOF
 HATCH TO GAIN ACCESS TO THE MECHANICAL EQUIPMENT ON THE
 ROOF. SHEET 047-A-301 SHOWS A VERTICAL DISTANCE FROM
 THE FINISH FLOOR TO THE BOTTOM OF THE BAR JOIST OF
 14.66 FEET, CENTERED IN THE SERVICE BAY DOORWAY. THE
 VERTICAL DISTANCE FROM FINISH FLOOR TO THE TOP OF THE
 ROOF AT THE ROOF HATCH IS OVER 18.50 FEET. PLEASE SHOW
 HOW COMPLIANCE WITH 306.5 OF THE 2017 MECHANICAL CODE
 WILL BE MET:
 2017 FBC-MECHANICAL. 306.5 EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE
 LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A
 BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER
 THAN 16 FEET (4877 MM) ABOVE GRADE TO ACCESS SUCH
 EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS
 OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) IN HEIGHT.
  
 RESPONSE:
 UNABLE TO FIND DETAIL A6/A-503 FOR ROOF LADDER. PROVIDE
 INFORMATION SHOWING COMPLIANCE.
  
 2B) OK.
 2C) OK.
 3) OK.
 4) OK.
 5) OK
  
 ORIGINAL COMMENT:
 6) 3RD REQUEST. THE SUBMITTED NOA: 14-0827.18TAMKO
 MODIFIED BITUMEN ROOF SYSTEM OVER STEEL DECK HAS
 VARIOUS SUB-SYSTEMS LISTED WITHIN THE REPORT BUT NONE
 OF THE SUB-SYSTEMS WERE IDENTIFIED AS THE ONE BEING
 INSTALLED. : FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 (LIMITATION #7 ALLOWS ENHANCED FASTENING, LIMITATION #
 9 DOES NOT ALLOW ENHANCED FASTENING) FOR ROOF ZONES 2 &
 3. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 RESPONSE:
 APPROVED ASSEMBLY WAS NOT SELECTED. AND, NEED SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR SELECTED ASSEMBLY
 (GENERAL LIMITATION #7 ONLY). IF THE SELECTED ASSEMBLY
 IS LIMITED BY GENERAL LIMITATION #9 AND THE ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN IT CAN NOT BE USED.
 NOTE: ALL PRODUCT APPROVALS CAN BE SUBMITTED LATER AS
 DEFERRED SUBMITTAL. ADVICE IF PREFER TO SUBMIT PRODUCT
 APPROVALS AS DEFERRED SUBMITTAL.
  
 ORIGINAL COMMENT:
 7) 3RD REQUEST. THE SUBMITTAL NOA: 16-0219.01 TC-5
 SERIES STEEL ROOF CURB FOR TRANE ROOF TOP UNITS. PLEASE
 REVIEW SHEET 4 AND 5 OF THE PRODUCT APPROVAL FOR
 TECHNICAL NOTES. RESTRAINT BRACKET QUANTITY IS
 DETERMINED BY PROJECT SPECIFIC CALCULATIONS, PERFORMED
 BY A FLORIDA LICENSED PE OR FLORIDA REGISTERED
 ARCHITECT THAT CONSIDER THE UNIQUE COMBINATION OF THE
 UNIT SIZE AND APPLICABLE LATERAL AND UPLIFT PRESSURES
 FOR EACH JOB. PLEASE PROVIDE CALCULATION FOR HOW MANY
 BRACKETS WILL BE NEEDED FOR EACH TYPE OF UNIT.
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. 2017
 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 RESPONSE:
 PLEASE CLARIFY ROOFTOP MECHANICAL UNIT CURB AND
 ATTACHMENT RESPONSE LETTER. THE SECOND PARAGRAPH OF THE
 LETTER STATS THAT 2 BRACKETS ARE REQUIRED PER SIDE FOR
 A TOTAL OF 4 BRACKETS EACH UNIT. IF TWO BRACKETS ARE
 REQUIRED PER SIDE, THEN THE TOTAL IS 8 BRACKETS PER
 UNIT NOT 4. CLARIFY/REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
  
 ORIGINAL COMMENT:
 8) 3RD REQUEST. THE SUBMITTAL NOA: 17-1017.14 TRULITE
 SERIES 3100 REGISTER ALUMINUM STOREFRONT/ WINDOW WALL
 SYSTEM- L. M. I. SHEETS 2-5 DO NOT OPEN FOR REVIEW.
 PLEASE NOTE ON PAGE 6 ONLY THE BOTTOM SERIES OF GLASS
 IS HIGHLIGHTED FOR PRESSURES. THE UPPER WINDOW GLASS IS
 NOT MENTIONED. THE UPPER GLAZING UNITS WHICH HAVE BOTH
 VERTICAL AND HORIZONTAL FRAMING MEMBERS ARE NOT
 IDENTIFIED ON SHEETS 8 AND 9 OF THE REPORT NOR IS THE
 CHART HIGHLIGHTED OR CIRCLED TO IF THE JAMBS ARE
 REQUIRED TO BE STEEL RE-ENFORCED. SHEET 10 OF 17 THE
 DOOR MULLION INDICATES TRULITE DOORS ARE UNDER A
 SEPARATE NOA. SHEET 13 OF 17 THE ANCHOR LOAD CHART IS
 NOT IDENTIFIED AS TO THE TYPE OF ANCHOR FOR THE FRAME
 WIDTH AND HEIGHT.
 IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 RESPONSE:
 NEED TO PROVIDE THE NOA FOR TRULITE DOORS AS SPECIFIED
 ON THE STOREFRONT NOA AND AS SHOWN ON PLANS.
  
 9) OK.
 10) OK
 11) OK
 12) OK
  
 13) INFORMATIONAL: ART IN PUBLIC PLACES
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 14) IMPACT FEES - SEE IMPACT FEES REVIEW STOP FOR
 PROCEDURE.
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  