2019-11-08 16:55:11 | NEW AUTOMOBILE DEALERSHIP, THIRD BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| |
| NOTICE: *************** 4X FEE / NOTICE!!!!! |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B) ****************** |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| 1) SHEET 002-G-101 THE LIFE SAFETY PLAN: |
| |
| ORIGINAL COMMENT: |
| 1A) 3RD REQUEST. UNDER THE HEADING BUILDING CODE |
| SUMMARY THE PROPOSED USE IS LISTED AS BUSINESS (B) AND |
| STORAGE (S1). PLEASE NOTE THAT THE SERVICE SHOP IS |
| LISTED AS A S1 OCCUPANCY. FOR MOTOR VEHICLE REPAIR |
| GARAGES COMPLYING WITH THE MAXIMUM ALLOWABLE QUANTITIES |
| OF HAZARDOUS MATERIALS LISTED IN TABLE 307.1(1). |
| PLEASE SUBMIT A LIST OF HAZARDOUS MATERIALS AND |
| ALLOWABLE QUANTITIES PER THE 2017 FBC-B TABLE 307.1(1). |
| |
| RESPONSE: |
| THE SAME RESPONSE THAT WAS PROVIDED ON THE PREVIOUS |
| COMMENT WAS PROVIDED THIS TIME AGAIN. THE ONLY |
| DIFFERENCE IS THAT THE NOTE "G-101 NOTE ADDED (CLOUD |
| 3)" WAS ADDED. |
| THIS DOESN'T ANSWER THE REQUEST FROM THE PREVIOUS |
| REVIEWER. THE REQUEST IS TO PROVIDE THE LIST AND |
| QUANTITIES OF EACH HAZARDOUS MATERIALS THAT ARE GOING |
| TO BE STORED IN THIS PLACE. ALSO, CLEARLY SHOW ON PLANS |
| LOCATION OF EACH MATERIAL. ARCHITECT MAY WANT TO |
| COORDINATE THIS INFORMATION WITH THE OWNER OF THE |
| DEALERSHIP TO VERIFY QUANTITIES OF EACH MATERIAL TO BE |
| STORED IN THIS PLACE AND PROVIDE INFORMATION ON |
| DRAWINGS. |
| |
| |
| 1B) OK |
| |
| ORIGINAL COMMENT: |
| 1C) SEMI-COMPLIED. UNDER THE BUILDING DATA THERE IS NO |
| LISTING FOR THE REQUIRED AREA OF REFUGE, THIS IS A 2 |
| STORY BUILDING AND NO FIRE SPRINKLERS. THE 2017 |
| FBC-ACCESSIBILITY CODE UNDER SECTION 207 ACCESSIBLE |
| MEANS OF EGRESS. SECTION 207.1. MEANS OF EGRESS SHALL |
| COMPLY WITH SECTION 1007 OF THE INTERNATIONAL BUILDING |
| CODE (2003 EDITION). |
| PLEASE REVIEW IN THE 2003 IBC-B SECTIONS DEALING WITH: |
| |
| 1007.3 ENCLOSED EXIT STAIRWAYS, 48 INCHES BETWEEN |
| HANDRAILS. |
| RESPONSE: |
| OK. DIMENSIONS ON PLANS WERE REVISED, BUT INFORMATION |
| ON SHEET G101 WAS NOT REVISED. REVISE AS REQUIRED TO |
| MATCH. |
| |
| 1007.4 ELEVATORS. |
| RESPONSE: |
| OK. NO USED AS MEANS OF EGRESS. |
| |
| 1007.6 AREAS OF REFUGE. |
| RESPONSE: |
| OK. BUT, CLEARLY IDENTITY ON PLANS "AREA OF REFUGE AND |
| SPECIFY SIZE. |
| |
| 1007.6.1. SIZE. |
| RESPONSE: |
| CLEARLY IDENTITY ON PLANS "AREA OF REFUGE AND SPECIFY |
| SIZE. |
| |
| 1007.6.2. SEPARATION. |
| RESPONSE: |
| OK. NO REQUIRED. |
| |
| 1007.6.3. TWO-WAY COMMUNICATION. |
| RESPONSE: |
| OK. BUT NEED TO CLEARLY SPECIFY IT ON PLANS. AND, TWO |
| WAY COMMUNICATIONS SHALL INCLUDE BOTH AUDIBLE AND |
| VISIBLE SIGNALS. |
| |
| 1007.6.4. INSTRUCTIONS. |
| RESPONSE: |
| CLEARLY SPECIFY ON PLANS REQUIRED INSTRUCTIONS. |
| |
| 1007.6.5. IDENTIFICATION. |
| RESPONSE: |
| CLEARLY PROVIDE ON PLANS THE IDENTIFICATION |
| INFORMATION. |
| |
| 1007.7.7. SIGNAGE. |
| RESPONSE: |
| CLEARLY SPECIFY ON PLANS SIGNAGE THAT ELEVATOR IS NOT |
| AN APPROVED ACCESSIBLE MEANS OF EGRESS AND INDICATE |
| LOCATION OF ACCESSIBLE MEANS OF EGRESS. |
| |
| |
| ORIGINAL COMMENT: |
| 1D) 3RD REQUEST. SEPARATED MIXED OCCUPANCY SHOWS THE |
| FORMULA FOR AREA CALCULATIONS BUT HAS LEFT THE |
| CALCULATION BLANK. PLEASE PROVIDE THE ACTUAL AND |
| ALLOWABLE SQUARE FEET FOR EACH OF THE OCCUPANCIES AND |
| THE END CALCULATION. 2017 FBC-B 508.3.3. |
| |
| RESPONSE: |
| OCCUPANCIES LISTED ON SHEET G-101 (A AND M OCCUPANCIES) |
| DON'T CORRESPOND TO THE OCCUPANCIES LISTED UNDER |
| "ALLOWABLE AREA" (B AND S-1 OCCUPANCIES). REVISE AS |
| REQUIRED. |
| |
| |
| ORIGINAL COMMENT: |
| 1E) SEMI-COMPLIED. PLEASE NOTE THE PLANS DOES NOT STATE |
| THE ACTUAL OCCUPANT LOAD FOR EACH OF THE OCCUPANCIES. |
| THE EXIT WIDTH DOES PROVIDE THE AREA FOR EACH OCCUPANCY |
| AND AREA PER OCCUPANT (TABLE 1004.1.2) BUT DOES NOT |
| GIVE THE ACTUAL OCCUPANT LOAD PER STORY AND THE TOTAL |
| OCCUPANT LOAD. 2017 FBC-B 1004.1 & TABLE 1004.1.2. |
| |
| RESPONSE: |
| INFORMATION SHOWN ON THE "EGRESS WIDTH" TABLE AND |
| INFORMATION SHOWN ON PLANS DON'T MATCH. PROVIDE THE |
| NUMBER OF PEOPLE FOR EACH OCCUPANCY BASED ON THE GROSS |
| SQUARE FOOTAGE AS REQUIRED BY TABLE 1004.1.2 |
| FBC-BUILDING. AND, COORDINATE WITH NUMBER OF PEOPLE |
| SHOWN ON FLOOR PLANS FOR EACH OCCUPANCY. CLARIFY WHY ON |
| THE SECOND FLOOR THERE ARE MORE CHAIRS THAN NUMBER OF |
| PEOPLE SPECIFIED?. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| ALSO, REVISE INFORMATION ON THE EXIT WIDTH TABLE. |
| REVISE SIZE OF STAIRS TO MATCH PLANS REVISED TO COMPLY |
| WITH THE ACCESSIBILITY REQUIREMENTS. AND, REVISE THE |
| "EGRESS CAPACITY FACTOR" OF THE STAIRS TO COMPLY WITH |
| SEC. 1005.3.1 FBC-BUILDING. THE FACTOR IS 0.3 NOT 0.2. |
| |
| IN ADDITION, REVISE THE ACTUAL WIDTH OF OPENINGS FOR |
| "OTHER EGRESS COMPONENTS" ( EGRESS DOORS FOR EXAMPLE). |
| SEE SEC. 1010.1.1 FBC-BUILDING FOR ACTUAL SIZE OF |
| EGRESS DOORS AND REVISE INFORMATION ON PLANS AS |
| REQUIRED. |
| |
| |
| ORIGINAL COMMENT: |
| 1F)KEY NOTES ON SHEET 041-A-101 INDICATE THE DESIGNER |
| OF RECORD REQUIRING A 2 HOUR WALL BETWEEN THE B & S1 |
| OCCUPANCY AND DECLARING THE BLOCK TO COMPLY WITH |
| (U905). THIS DESIGN REQUIRES A D-2 A 8 INCH BLOCK, AND |
| 2 HOUR FIRE RATED CONCRETE BLOCK. PLEASE NOTE WE WILL |
| REQUIRE DOCUMENTATION FROM THE BLOCK MANUFACTURER THAT |
| THEIR 2 HOUR RATING OF BLOCK COMPLIES WITH TABLE |
| 722.3.2. (2017 FBC-B) MINIMUM EQUIVALENT THICKNESS OF |
| BEARING OR NONBEARING CONCRETE MASONRY WALLS. PROVIDE |
| THE TYPE OF AGGREGATE AND EQUIVALENT THICKNESS FOR THE |
| 2 HOUR FIRE RATING. THE SAME FOR 12 INCH WIDE BLOCK, |
| PROVIDE A LETTER FROM THE BLOCK MANUFACTURER. |
| |
| RESPONSE: |
| WALL TYPES AND PLANS ARE NOT CLEAR. MISSING DETAILS FOR |
| THE SPECIFIED FIRE RATED WALLS. PROVIDE COMPLETE WALL |
| DETAIL FOR THE 2 HOUR FIRE RATED CONCRETE BLOCK WALLS |
| (U905) SPECIFYING 2HR BLOCK. ALSO, PROVIDE COMPLETE |
| WALL DETAIL FOR THE ONE HOUR FIRE RATED PARTITION |
| (U419). AND, CLEARLY TAG THEM ON THE FLOOR PLANS. IN |
| ADDITION, CLEARLY SPECIFY IF IT'S 8" OR 12" CONCRETE |
| BLOCK. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 1G) 3RD REQUEST. SHEET A-501 WALL TYPES A3-A6 ALL SHOW |
| BLOCK WALLS WITH EITHER 8 INCH OR 12 INCH CMU. EACH |
| DETAIL SHOULD BE SPECIFIC TO BLOCK TYPE AND WALL TYPE. |
| AGAIN THESE DETAILS DO NOT MATCH THE WALL |
| IDENTIFICATION TAGS LOCATED IN SHEETS 041-A-101 AND |
| 042-A-102. INFORMATION ON THE PLANS HAS TO BE SPECIFIC |
| NO EITHER, OR. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| RESPONSE: |
| SEE RESPONSE FOR ITEM 1(F) ABOVE. |
| |
| 1H) OK. |
| |
| |
| |
| ORIGINAL COMMENT: |
| SECOND ROUND OF COMMENTS. THE LIFE SAFETY SHEET |
| 002-G-101 SHOWS A SECOND STORY BUSINESS AND STORAGE |
| OCCUPANCY, (ASSUMED S-1). THE TRAVEL DISTANCE IS SHOWN |
| GOING DOWN THROUGH THE STAIRWAY MAKING THIS STAIRWAY |
| EXIT ACCESS AND THE TRAVEL DISTANCE ON THE STAIRS TO BE |
| TAKEN PARALLEL TO THE STAIRS. FROM THE FURTHEST POINT |
| TAKEN ON THE SECOND FLOOR TO THE FIRST FLOOR LANDING |
| THE TRAVEL DISTANCE IS BETWEEN 85 TO 90 FEET. THIS IS |
| OVER THE ALLOWABLE MAXIMUM COMMON PATH OF TRAVEL FROM |
| TABLE 1006.3.2(2) OF 75 FEET AND OCCUPANT LOAD OF 49 |
| FOR BUSINESS OR 29 FOR STORAGE OCCUPANCY. IF THE |
| STAIRWAY WAS A RATED 1 HOUR EXIT STAIRWAY WITH OPENING |
| PROTECTIVES AND EXIT PASSAGEWAY TO THE EXTERIOR, THEN |
| THE TRAVEL DISTANCE FOR THE 2ND FLOOR WOULD WORK. |
| PLEASE REVIEW ALL OF THE REQUIREMENTS FOR EXIT AND EXIT |
| PASSAGEWAYS. EXIT PASSAGEWAYS ARE FOUND UNDER FBC-B |
| 1024. PLEASE REVIEW VENTILATION REQUIREMENTS (FBC-B |
| 1024.7) FOR EXIT PASSAGEWAYS AS WELL. |
| |
| RESPONSE: |
| THIS IS A TWO STORY BUILDING. TABLE 1006.3.2(2) |
| FBC-BUILDING IS THE TABLE THAT APPLIES TO THIS |
| BUILDING. IF THERE IS A DIFFERENCE BETWEEN THE FIRE |
| CODE AND BUILDING CODE THEN THE MOST STRINGENT CODE |
| PREVAILS. IT LOOKS LIKE THE STAIRWAY IS GOING TO BE AT |
| LEAST ONE HOUR FIRE RATED. REVISE TRAVEL DISTANCE. SHOW |
| TRAVEL DISTANCE UP TO THE ENTRY OF THE STAIRWAY. |
| |
| |
| ORIGINAL COMMENT: |
| 1J) 3RD REQUEST. VERSION # 2 STILL DOES NOT SHOW |
| COMPLIANCE WITH FBC-B 1015.4 OPENING LIMITATIONS. |
| REQUIRED GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW |
| PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM |
| THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT. ALSO |
| THERE IS A DETAIL FOR RISE AND RUN BUT NO DIMENSION FOR |
| COMPLIANCE WITH 1015.4 FBC-B EXCEPTION 2. THE |
| TRIANGULAR OPENINGS AT THE OPEN SIDES OF A STAIR, |
| FORMED BY THE RISER, TREAD AND BOTTOM RAIL SHALL NOT |
| ALLOW PASSAGE OF A SPHERE 6 INCHES IN DIAMETER. |
| 1 ST ROUND OF COMMENTS. STAIRWAY GUARDRAIL. SHEET |
| 049-A-101. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE |
| WITH: 2017 FBC-B 1015.4 OPENING LIMITATIONS. REQUIRED |
| GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW PASSAGE OF A |
| SPHERE 4 INCHES (102 MM) IN DIAMETER FROM THE WALKING |
| SURFACE TO THE REQUIRED GUARD HEIGHT. |
| |
| RESPONSE: |
| STAIR SECTION A4 ON SHEET 049-A-401 SPECIFIES 4" |
| BETWEEN THE HORIZONTAL RAILING. THE DIMENSION NEEDS TO |
| BE SMALLER THAN 4 INCHES SO IT DOESN'T ALLOW THE |
| PASSAGE OF 4" SPHERE. REVISE AS REQUIRED. |
| ALSO, THE REQUESTED INFORMATION FOR THE LIMITATIONS ON |
| THE TRIANGULAR AREA AT THE OPEN SIDE OF THE STAIRS WAS |
| NOT PROVIDED. PROVIDE COMPLETE INFORMATION. |
| |
| |
| ORIGINAL COMMENT: |
| 2A) 3RD REQUEST. THERE MUST BE A PERMANENT MEANS OF |
| EGRESS TO REACH THE ROOF TOP HATCH. |
| 1ST ROUND OF COMMENTS. SHEET 042-A102 THE 2ND FLOOR |
| PLAN AND ROOF PLAN OF THE REPAIR GARAGE, SHOWS A ROOF |
| HATCH TO GAIN ACCESS TO THE MECHANICAL EQUIPMENT ON THE |
| ROOF. SHEET 047-A-301 SHOWS A VERTICAL DISTANCE FROM |
| THE FINISH FLOOR TO THE BOTTOM OF THE BAR JOIST OF |
| 14.66 FEET, CENTERED IN THE SERVICE BAY DOORWAY. THE |
| VERTICAL DISTANCE FROM FINISH FLOOR TO THE TOP OF THE |
| ROOF AT THE ROOF HATCH IS OVER 18.50 FEET. PLEASE SHOW |
| HOW COMPLIANCE WITH 306.5 OF THE 2017 MECHANICAL CODE |
| WILL BE MET: |
| 2017 FBC-MECHANICAL. 306.5 EQUIPMENT AND APPLIANCES ON |
| ROOFS OR ELEVATED STRUCTURES. |
| WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE |
| LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A |
| BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER |
| THAN 16 FEET (4877 MM) ABOVE GRADE TO ACCESS SUCH |
| EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS |
| OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT |
| REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 |
| INCHES (762 MM) IN HEIGHT. |
| |
| RESPONSE: |
| UNABLE TO FIND DETAIL A6/A-503 FOR ROOF LADDER. PROVIDE |
| INFORMATION SHOWING COMPLIANCE. |
| |
| 2B) OK. |
| 2C) OK. |
| 3) OK. |
| 4) OK. |
| 5) OK |
| |
| ORIGINAL COMMENT: |
| 6) 3RD REQUEST. THE SUBMITTED NOA: 14-0827.18TAMKO |
| MODIFIED BITUMEN ROOF SYSTEM OVER STEEL DECK HAS |
| VARIOUS SUB-SYSTEMS LISTED WITHIN THE REPORT BUT NONE |
| OF THE SUB-SYSTEMS WERE IDENTIFIED AS THE ONE BEING |
| INSTALLED. : FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED |
| (LIMITATION #7 ALLOWS ENHANCED FASTENING, LIMITATION # |
| 9 DOES NOT ALLOW ENHANCED FASTENING) FOR ROOF ZONES 2 & |
| 3. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| 1609.6.4.4.1 COMPONENTS & CLADDING. |
| |
| RESPONSE: |
| APPROVED ASSEMBLY WAS NOT SELECTED. AND, NEED SIGNED |
| AND SEALED RAS 117 CALCULATIONS FOR SELECTED ASSEMBLY |
| (GENERAL LIMITATION #7 ONLY). IF THE SELECTED ASSEMBLY |
| IS LIMITED BY GENERAL LIMITATION #9 AND THE ASSEMBLY |
| DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, |
| THEN IT CAN NOT BE USED. |
| NOTE: ALL PRODUCT APPROVALS CAN BE SUBMITTED LATER AS |
| DEFERRED SUBMITTAL. ADVICE IF PREFER TO SUBMIT PRODUCT |
| APPROVALS AS DEFERRED SUBMITTAL. |
| |
| ORIGINAL COMMENT: |
| 7) 3RD REQUEST. THE SUBMITTAL NOA: 16-0219.01 TC-5 |
| SERIES STEEL ROOF CURB FOR TRANE ROOF TOP UNITS. PLEASE |
| REVIEW SHEET 4 AND 5 OF THE PRODUCT APPROVAL FOR |
| TECHNICAL NOTES. RESTRAINT BRACKET QUANTITY IS |
| DETERMINED BY PROJECT SPECIFIC CALCULATIONS, PERFORMED |
| BY A FLORIDA LICENSED PE OR FLORIDA REGISTERED |
| ARCHITECT THAT CONSIDER THE UNIQUE COMBINATION OF THE |
| UNIT SIZE AND APPLICABLE LATERAL AND UPLIFT PRESSURES |
| FOR EACH JOB. PLEASE PROVIDE CALCULATION FOR HOW MANY |
| BRACKETS WILL BE NEEDED FOR EACH TYPE OF UNIT. |
| 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. 2017 |
| FBC-M- 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT, |
| APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL |
| BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES |
| DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| CODE, BUILDING. |
| |
| RESPONSE: |
| PLEASE CLARIFY ROOFTOP MECHANICAL UNIT CURB AND |
| ATTACHMENT RESPONSE LETTER. THE SECOND PARAGRAPH OF THE |
| LETTER STATS THAT 2 BRACKETS ARE REQUIRED PER SIDE FOR |
| A TOTAL OF 4 BRACKETS EACH UNIT. IF TWO BRACKETS ARE |
| REQUIRED PER SIDE, THEN THE TOTAL IS 8 BRACKETS PER |
| UNIT NOT 4. CLARIFY/REVISE AS REQUIRED. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| |
| ORIGINAL COMMENT: |
| 8) 3RD REQUEST. THE SUBMITTAL NOA: 17-1017.14 TRULITE |
| SERIES 3100 REGISTER ALUMINUM STOREFRONT/ WINDOW WALL |
| SYSTEM- L. M. I. SHEETS 2-5 DO NOT OPEN FOR REVIEW. |
| PLEASE NOTE ON PAGE 6 ONLY THE BOTTOM SERIES OF GLASS |
| IS HIGHLIGHTED FOR PRESSURES. THE UPPER WINDOW GLASS IS |
| NOT MENTIONED. THE UPPER GLAZING UNITS WHICH HAVE BOTH |
| VERTICAL AND HORIZONTAL FRAMING MEMBERS ARE NOT |
| IDENTIFIED ON SHEETS 8 AND 9 OF THE REPORT NOR IS THE |
| CHART HIGHLIGHTED OR CIRCLED TO IF THE JAMBS ARE |
| REQUIRED TO BE STEEL RE-ENFORCED. SHEET 10 OF 17 THE |
| DOOR MULLION INDICATES TRULITE DOORS ARE UNDER A |
| SEPARATE NOA. SHEET 13 OF 17 THE ANCHOR LOAD CHART IS |
| NOT IDENTIFIED AS TO THE TYPE OF ANCHOR FOR THE FRAME |
| WIDTH AND HEIGHT. |
| IDENTIFY GLAZING/ MULLIONS. |
| PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| RESPONSE: |
| NEED TO PROVIDE THE NOA FOR TRULITE DOORS AS SPECIFIED |
| ON THE STOREFRONT NOA AND AS SHOWN ON PLANS. |
| |
| 9) OK. |
| 10) OK |
| 11) OK |
| 12) OK |
| |
| 13) INFORMATIONAL: ART IN PUBLIC PLACES |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| 822-1515 E-MAIL: [email protected] |
| |
| 14) IMPACT FEES - SEE IMPACT FEES REVIEW STOP FOR |
| PROCEDURE. |
| |
| 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |