2019-08-21 16:03:44PLUMBING 2ND REVIEW**DENIED**
 LAST REVIEW COMMENTS STILL NOT ANSWERED
 1-PROVIDE CLEAR FLOOR SPACE AND TURNING SPACE FOR THE
 TRAINING ROOM/ BREAK ROOM SINK WITH CABINET DETAIL
 SHOWING MAX 34?. FBC-ACC 606.2, 606.3
 2- PROVIDE NOTE ON PLAN SEPARATE BACKFLOW AND
 INTERCEPTOR PERMIT REQUIRED. FBC 107.1
 3-SHT. A-106 IS CALLING OUT ROOF DRAIN CALCULATIONS
 BASED ON 2010 FBC-PLB CODE. THE CODE CURRENTLY IS THE
 2017 6TH ED. PROVIDE SIZING OF THE STORM SYSTEM PER
 FBC-PLB 1105.2, 1106.2
 4- SHT. A-106 CALL OUT PIPE PITCHED PER FBC-PLB 553.10.
 PLEASE CLARIFY. FBC 107.1
 5-SHT. A-301 SHOWS ROOF PITCH AS 1/4? PER FOOT BUT
 DRAIN DETAIL CALLS OUT ?? PER FOOT. PLEASE CLARIFY. FBC
 107.1
 6-SHT. A-401 MIRROR DETAIL SHOWS MOUNTING AT 3?4? (40?)
 TO THE BOTTOM OF THE MIRROR. MAX MEASUREMENT SHALL BE
 TO THE REFLECTING SURFACE. FBC-ACC 603.3