Plan Review Notes For Permit 19040448 |
Permit Number |
19040448 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-08-21 16:03:44 | PLUMBING 2ND REVIEW**DENIED** | | LAST REVIEW COMMENTS STILL NOT ANSWERED | | 1-PROVIDE CLEAR FLOOR SPACE AND TURNING SPACE FOR THE | | TRAINING ROOM/ BREAK ROOM SINK WITH CABINET DETAIL | | SHOWING MAX 34?. FBC-ACC 606.2, 606.3 | | 2- PROVIDE NOTE ON PLAN SEPARATE BACKFLOW AND | | INTERCEPTOR PERMIT REQUIRED. FBC 107.1 | | 3-SHT. A-106 IS CALLING OUT ROOF DRAIN CALCULATIONS | | BASED ON 2010 FBC-PLB CODE. THE CODE CURRENTLY IS THE | | 2017 6TH ED. PROVIDE SIZING OF THE STORM SYSTEM PER | | FBC-PLB 1105.2, 1106.2 | | 4- SHT. A-106 CALL OUT PIPE PITCHED PER FBC-PLB 553.10. | | PLEASE CLARIFY. FBC 107.1 | | 5-SHT. A-301 SHOWS ROOF PITCH AS 1/4? PER FOOT BUT | | DRAIN DETAIL CALLS OUT ?? PER FOOT. PLEASE CLARIFY. FBC | | 107.1 | | 6-SHT. A-401 MIRROR DETAIL SHOWS MOUNTING AT 3?4? (40?) | | TO THE BOTTOM OF THE MIRROR. MAX MEASUREMENT SHALL BE | | TO THE REFLECTING SURFACE. FBC-ACC 603.3 | | TIM HUNT | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | THUNT@CGASOLUTIONS | | 561-248-2703 | | |
|