Plan Review Notes
Plan Review Notes For Permit 19040448
Permit Number 19040448
Review Stop B
Sequence Number 2
Notes
Date Text
2019-08-12 11:49:532017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040448
 ADD: 2700 S AUSTRALIAN AVE.
 CONT: AUTOBUILDERS GENERAL CONT. SVCS. INC.
 TEL: 561-622-3515
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2ND REVIEW
 DATE: MONDAY, AUGUST 12TH/2019
 ACTION: DENIED
  
 NOTICE: *************** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B) ******************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) SHEET 002-G-101 THE LIFE SAFETY PLAN:
 1A).2ND REQUEST. UNDER THE HEADING BUILDING CODE
 SUMMARY THE PROPOSED USE IS LISTED AS BUSINESS (B) AND
 STORAGE (S1). PLEASE NOTE THAT THE SERVICE SHOP IS
 LISTED AS A S1 OCCUPANCY. FOR MOTOR VEHICLE REPAIR
 GARAGES COMPLYING WITH THE MAXIMUM ALLOWABLE QUANTITIES
 OF HAZARDOUS MATERIALS LISTED IN TABLE 307.1(1).
 PLEASE SUBMIT A LIST OF HAZARDOUS MATERIALS AND
 ALLOWABLE QUANTITIES PER THE 2017 FBC-B TABLE 307.1(1).
  
 1B) 2N REQUEST. UNDER THE HEADING OF BUILDING DATA THE
 PLANS ARE INDICATED THEY ARE DESIGNED UNDER THE 2014
 FBC. PLEASE NOTE THAT THE 2017 FBC-B WAS ADOPTED
 STATEWIDE ON DEC. 31/ 2017. PLEASE UPDATE PLANS.
  
 1C) 2ND REQUEST. UNDER THE BUILDING DATA THERE IS NO
 LISTING FOR THE REQUIRED AREA OF REFUGE, THIS IS A 2
 STORY BUILDING AND NO FIRE SPRINKLERS. THE 2017
 FBC-ACCESSIBILITY CODE UNDER SECTION 207 ACCESSIBLE
 MEANS OF EGRESS. SECTION 207.1. MEANS OF EGRESS SHALL
 COMPLY WITH SECTION 1007 OF THE INTERNATIONAL BUILDING
 CODE (2003 EDITION).
 PLEASE REVIEW IN THE 2003 IBC-B SECTIONS DEALING WITH:
 1007.3 ENCLOSED EXIT STAIRWAYS, 48 INCHES BETWEEN
 HANDRAILS.
 1007.4 ELEVATORS.
 1007.6 AREAS OF REFUGE.
 1007.6.1. SIZE.
 1007.6.2. SEPARATION.
 1007.6.3. TWO-WAY COMMUNICATION.
 1007.6.4. INSTRUCTIONS.
 1007.6.5. IDENTIFICATION.
 1007.7.7. SIGNAGE.
  
 1D) 2ND REQUEST. SEPARATED MIXED OCCUPANCY SHOWS THE
 FORMULA FOR AREA CALCULATIONS BUT HAS LEFT THE
 CALCULATION BLANK. PLEASE PROVIDE THE ACTUAL AND
 ALLOWABLE SQUARE FEET FOR EACH OF THE OCCUPANCIES AND
 THE END CALCULATION. 2017 FBC-B 508.3.3.
  
 1E) COMPLIED. PLEASE NOTE THE PLANS DOES NOT STATE THE
 ACTUAL OCCUPANT LOAD FOR EACH OF THE OCCUPANCIES. THE
 EXIT WIDTH DOES PROVIDE THE AREA FOR EACH OCCUPANCY AND
 AREA PER OCCUPANT (TABLE 1004.1.2) BUT DOES NOT GIVE
 THE ACTUAL OCCUPANT LOAD PER STORY AND THE TOTAL
 OCCUPANT LOAD. 2017 FBC-B 1004.1 & TABLE 1004.1.2.
  
 1F)SEMI-COMPLIED. KEY NOTES ON SHEET 041-A-101 INDICATE
 THE DESIGNER OF RECORD REQUIRING A 2 HOUR WALL BETWEEN
 THE B & S1 OCCUPANCY AND DECLARING THE BLOCK TO COMPLY
 WITH (U905). THIS DESIGN REQUIRES A D-2 A 8 INCH BLOCK,
 AND 2 HOUR FIRE RATED CONCRETE BLOCK. PLEASE NOTE WE
 WILL REQUIRE DOCUMENTATION FROM THE BLOCK MANUFACTURER
 THAT THEIR 2 HOUR RATING OF BLOCK COMPLIES WITH TABLE
 722.3.2. (2017 FBC-B) MINIMUM EQUIVALENT THICKNESS OF
 BEARING OR NONBEARING CONCRETE MASONRY WALLS. PROVIDE
 THE TYPE OF AGGREGATE AND EQUIVALENT THICKNESS FOR THE
 2 HOUR FIRE RATING. THE SAME FOR 12 INCH WIDE BLOCK,
 PROVIDE A LETTER FROM THE BLOCK MANUFACTURER.
 THE OTHER ISSUE WITH NOTES 10 AND 11 GO BACK TO THE
 WORD OR, 8 INCH OR 12 INCH BLOCK. THE REQUIREMENT HAS
 TO BE SPECIFIC. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATIVE CODE
 SECTION 107.2.1.3. DRAWINGS & SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES
 "SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 1ST ROUND COMMENT. THE LIFE SAFETY SHEET 002-G-101
 UNDER THE HEADING OF ALLOWABLE AREA, MIXED OCCUPANCY
 INDICATES YES, AND SEPARATION 2 HRS. THE FIRST FLOOR
 PARTS ROOM HAS A NOTE 2 HRS. IT WOULD APPEAR THAT THIS
 NOTE REFERS TO THE BLOCK WALL BETWEEN THE BUSINESS
 OCCUPANCY AND S1 REPAIR GARAGE. THE FIRST FLOOR PLAN
 SHEET 041-A-101 HAS THIS SAME WALL WITH A WALL
 IDENTIFICATION TAG IDENTIFIED AS WALL TYPE 10. SHEET
 042-A-102 THE SECOND FLOOR HAS THE SAME WALL TYPE
 IDENTIFIED WITH A WALL IDENTIFICATION TAG AS WALL TYPE
 6. WHEN YOU OPEN UP SHEET 050-A-501 WALL TYPES NONE OF
 THE WALL TYPES SHOWN HAVE THE SAME NAMING CONVENTION.
  
 1G) 2ND REQUEST. SHEET A-501 WALL TYPES A3-A6 ALL SHOW
 BLOCK WALLS WITH EITHER 8 INCH OR 12 INCH CMU. EACH
 DETAIL SHOULD BE SPECIFIC TO BLOCK TYPE AND WALL TYPE.
 AGAIN THESE DETAILS DO NOT MATCH THE WALL
 IDENTIFICATION TAGS LOCATED IN SHEETS 041-A-101 AND
 042-A-102. INFORMATION ON THE PLANS HAS TO BE SPECIFIC
 NO EITHER, OR. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 1H) INFORMATIONAL ONLY. PLEASE NOTE THE DESIGNER OF
 RECORD CAN DESIGN TO A MORE STRINGENT STANDARD, BUT
 UNDER THE 2017
 FBC-B TABLE 508.4 THERE IS NO OCCUPANCY SEPARATION
 REQUIRED BETWEEN A B AND S1 OCCUPANCY. IF THERE IS A
 DIFFERENCE BETWEEN THE FIRE CODE AND BUILDING CODE THEN
 THE MOST STRINGENT CODE PREVAILS.
  
 1I) 2ND REQUEST, SEMI-COMPLIED. YOU HAVE NOT COMPLIED
 WITH THE REQUIREMENTS OF COMMENT 1-C. THIS IS NEW
 CONSTRUCTION, 2 STORY NOT SPRINKLERED REQUIRING AN AREA
 OF REFUGE.
 PLEASE REVIEW IN THE 2003 IBC-B SECTIONS DEALING WITH:
 1007.3 ENCLOSED EXIT STAIRWAYS, 48 INCHES BETWEEN
 HANDRAILS.
 1007.4 ELEVATORS.
 1007.6 AREAS OF REFUGE.
 1007.6.1. SIZE.
 1007.6.2. SEPARATION.
 1007.6.3. TWO-WAY COMMUNICATION.
 1007.6.4. INSTRUCTIONS.
 1007.6.5. IDENTIFICATION.
 1007.7.7. SIGNAGE.
  
  
 1ST ROUND OF COMMENTS. THE LIFE SAFETY SHEET 002-G-101
 SHOWS A SECOND STORY BUSINESS AND STORAGE OCCUPANCY,
 (ASSUMED
 S-1). THE TRAVEL DISTANCE IS SHOWN GOING DOWN THROUGH
 THE STAIRWAY MAKING THIS STAIRWAY EXIT ACCESS AND THE
 TRAVEL DISTANCE ON THE STAIRS TO BE TAKEN PARALLEL TO
 THE STAIRS. FROM THE FURTHEST POINT TAKEN ON THE SECOND
 FLOOR TO THE FIRST FLOOR LANDING THE TRAVEL DISTANCE IS
 BETWEEN 85 TO 90 FEET. THIS IS OVER THE ALLOWABLE
 MAXIMUM COMMON PATH OF TRAVEL FROM TABLE 1006.3.2(2) OF
 75 FEET AND OCCUPANT LOAD OF 49 FOR BUSINESS OR 29 FOR
 STORAGE OCCUPANCY. IF THE STAIRWAY WAS A RATED 1 HOUR
 EXIT STAIRWAY WITH OPENING PROTECTIVES AND EXIT
 PASSAGEWAY TO THE EXTERIOR, THEN THE TRAVEL DISTANCE
 FOR THE 2ND FLOOR WOULD WORK. PLEASE REVIEW ALL OF THE
 REQUIREMENTS FOR EXIT AND EXIT PASSAGEWAYS. EXIT
 PASSAGEWAYS ARE FOUND UNDER FBC-B 1024. PLEASE REVIEW
 VENTILATION REQUIREMENTS (FBC-B 1024.7) FOR EXIT
 PASSAGEWAYS AS WELL.
  
 1J) 2ND REQUEST. VERSION # 2 STILL DOES NOT SHOW
 COMPLIANCE WITH FBC-B 1015.4 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW
 PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM
 THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT. ALSO
 THERE IS A DETAIL FOR RISE AND RUN BUT NO DIMENSION FOR
 COMPLIANCE WITH 1015.4 FBC-B EXCEPTION 2. THE
 TRIANGULAR OPENINGS AT THE OPEN SIDES OF A STAIR,
 FORMED BY THE RISER, TREAD AND BOTTOM RAIL SHALL NOT
 ALLOW PASSAGE OF A SPHERE 6 INCHES IN DIAMETER.
 1 ST ROUND OF COMMENTS. STAIRWAY GUARDRAIL. SHEET
 049-A-101. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE
 WITH: 2017 FBC-B 1015.4 OPENING LIMITATIONS. REQUIRED
 GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW PASSAGE OF A
 SPHERE 4 INCHES (102 MM) IN DIAMETER FROM THE WALKING
 SURFACE TO THE REQUIRED GUARD HEIGHT.
  
 2A) 2ND REQUEST. THERE MUST BE A PERMANENT MEANS OF
 EGRESS TO REACH THE ROOF TOP HATCH.
 1ST ROUND OF COMMENTS. SHEET 042-A102 THE 2ND FLOOR
 PLAN AND ROOF PLAN OF THE REPAIR GARAGE, SHOWS A ROOF
 HATCH TO GAIN ACCESS TO THE MECHANICAL EQUIPMENT ON THE
 ROOF. SHEET 047-A-301 SHOWS A VERTICAL DISTANCE FROM
 THE FINISH FLOOR TO THE BOTTOM OF THE BAR JOIST OF
 14.66 FEET, CENTERED IN THE SERVICE BAY DOORWAY. THE
 VERTICAL DISTANCE FROM FINISH FLOOR TO THE TOP OF THE
 ROOF AT THE ROOF HATCH IS OVER 18.50 FEET. PLEASE SHOW
 HOW COMPLIANCE WITH 306.5 OF THE 2017 MECHANICAL CODE
 WILL BE MET:
 2017 FBC-MECHANICAL. 306.5 EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE
 LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A
 BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER
 THAN 16 FEET (4877 MM) ABOVE GRADE TO ACCESS SUCH
 EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS
 OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) IN HEIGHT.
  
 2B) 2ND REQUEST. 2017 FBC-B 1015.6 MECHANICAL
 EQUIPMENT. GUARDS SHALL BE PROVIDED WHERE APPLIANCES,
 EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER
 COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10
 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE
 GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE
 OF A SPHERE 21 INCHES IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES BEYOND EACH END OF SUCH
 APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 2C)2ND REQUEST. PLEASE ALSO PROVIDE CODE COMPLIANCE
 WITH: 2017 FBC-B ROOF HATCH EXCEPTION: IN BUILDINGS
 WITHOUT AN OCCUPIED ROOF, ACCESS TO THE ROOF SHALL BE
 PERMITTED TO BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN
 16 SQUARE FEET IN AREA AND HAVING A MINIMUM DIMENSION
 OF 2 FEET.
  
 3) 2ND REQUEST. SHEET 028-S-1.0. EARTHWORK GENERAL
 NOTES: NOTE # 1 INDICATES ALL EARTHWORK SHALL BE DONE
 IN ACCORDANCE WITH THE REQUIREMENTS OUTLINED IN THE
 GEOTECHNICAL REPORT BY UNIVERSAL ENGINEERING SCIENCES.
 REPORT # 16357, DATED APRIL 22, 2019. SUBMIT REPORT.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B 1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
 IF THE SOILS REPORT DOES NOT HAVE AN ELECTRONIC
 SIGNATURE, THEN SUBMIT ONE PAPER ORIGINAL WITH
 SIGNATURE AND SEAL. 61G15-23.002 ENGINEER SEAL
 SIGNATURE.
 1ST ROUND OF COMMENTS. SHEET 028-S-1.0. EARTHWORK
 GENERAL NOTES: NOTE # 1 INDICATES ALL EARTHWORK SHALL
 BE DONE IN ACCORDANCE WITH THE REQUIREMENTS OUTLINED IN
 THE GEOTECHNICAL REPORT BY XXXXXXX/ DATE: XXXXX,
 MINIMUM BEARING PRESSURE XXXXXXX. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B 1803.5.2 QUESTIONABLE
 SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 4) COMPLIED. PRESSURES ARE IN VASD AND PRESSURE ZONES
 1-5 ARE GOOD.
  
 5) PROVISO: THIS BUILDING HAS WELDED AND BOLTED STEEL
 CONNECTIONS, PLEASE PROVIDE COMPLIANCE WITH, THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 6) 2ND REQUEST. THE SUBMITTED NOA: 14-0827.18TAMKO
 MODIFIED BITUMEN ROOF SYSTEM OVER STEEL DECK HAS
 VARIOUS SUB-SYSTEMS LISTED WITHIN THE REPORT BUT NONE
 OF THE SUB-SYSTEMS WERE IDENTIFIED AS THE ONE BEING
 INSTALLED. : FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 (LIMITATION #7 ALLOWS ENHANCED FASTENING, LIMITATION #
 9 DOES NOT ALLOW ENHANCED FASTENING) FOR ROOF ZONES 2 &
 3. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 7) 2ND REQUEST. THE SUBMITTAL NOA: 16-0219.01 TC-5
 SERIES STEEL ROOF CURB FOR TRANE ROOF TOP UNITS. PLEASE
 REVIEW SHEET 4 AND 5 OF THE PRODUCT APPROVAL FOR
 TECHNICAL NOTES. RESTRAINT BRACKET QUANTITY IS
 DETERMINED BY PROJECT SPECIFIC CALCULATIONS, PERFORMED
 BY A FLORIDA LICENSED PE OR FLORIDA REGISTERED
 ARCHITECT THAT CONSIDER THE UNIQUE COMBINATION OF THE
 UNIT SIZE AND APPLICABLE LATERAL AND UPLIFT PRESSURES
 FOR EACH JOB. PLEASE PROVIDE CALCULATION FOR HOW MANY
 BRACKETS WILL BE NEEDED FOR EACH TYPE OF UNIT.
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. 2017
 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 8) 2ND REQUEST. THE SUBMITTAL NOA: 17-1017.14 TRULITE
 SERIES 3100 REGISTER ALUMINUM STOREFRONT/ WINDOW WALL
 SYSTEM- L. M. I. SHEETS 2-5 DO NOT OPEN FOR REVIEW.
 PLEASE NOTE ON PAGE 6 ONLY THE BOTTOM SERIES OF GLASS
 IS HIGHLIGHTED FOR PRESSURES. THE UPPER WINDOW GLASS IS
 NOT MENTIONED. THE UPPER GLAZING UNITS WHICH HAVE BOTH
 VERTICAL AND HORIZONTAL FRAMING MEMBERS ARE NOT
 IDENTIFIED ON SHEETS 8 AND 9 OF THE REPORT NOR IS THE
 CHART HIGHLIGHTED OR CIRCLED TO IF THE JAMBS ARE
 REQUIRED TO BE STEEL RE-ENFORCED. SHEET 10 OF 17 THE
 DOOR MULLION INDICATES TRULITE DOORS ARE UNDER A
 SEPARATE NOA. SHEET 13 OF 17 THE ANCHOR LOAD CHART IS
 NOT IDENTIFIED AS TO THE TYPE OF ANCHOR FOR THE FRAME
 WIDTH AND HEIGHT.
 IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 9) 2ND REQUEST. GENSTEEL SERIES GENSTORM OUTSWING DOOR
 NOA: 17-0803.01 PLEASE PROVIDE THE TYPE OF LOCK OPTION
 THAT WILL BE USED WITH THIS DOOR. SEE SHEET 9 OF 11.
  
 10) 2ND REQUEST. THE SUBMITTAL NOA: 17-1218.02 MIAMI
 TECH ALUMINUM A/C STAND. THE ROOF TOP A/C STAND PRODUCT
 APPROVAL A MIAMI-DADE NOA # 17-1218.02 WAS SUBMITTED,
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 11) THE PERMIT APPLICATION INDICATES THAT THE SQUARE
 FOOTAGE OF THE AUTO DEALERSHIP BEING 15,805 SQ. FT.
 THAT WOULD APPEAR TO BE THE 1ST FLOOR ONLY. THE TOTAL
 SQ. FOOTAGE I CALCULATED WAS 18,534.00 SQ. FT.
 DISCREPANCY IN SQ. FT.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 12) 2ND REQUEST. INFORMATION REQUIRED, SINCE THIS
 PROJECT IS A NEW AUTOMOBILE DEALERSHIP WILL THEY BE
 FILLING THE CARS WITH GASOLINE? I DIDN'T SEE TANKS ON
 ANY PLAN, ARE THEY TO BE ABOVE GROUND OR BENEATH THE
 GROUND? NOTE PETROLEUM TANKS ARE TO BE REVIEWED UNDER
 SEPARATE PERMIT, FEES AND REVIEWS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 13) INFORMATIONAL: ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 14) 2ND REQUEST. IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  