Plan Review Notes For Permit 19040448 |
Permit Number |
19040448 |
|
Review Stop |
SIGNATURE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-02 17:02:09 | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | PER FLORIDA STATUTE 471, 481 | | | | 1. NEW PAGES SUBMITTED IN SUBSEQUENT REVIEW CYCLES | | REQUIRE VERIFICATION. | | | | 2. THE ARCHITECT'S SEAL (BRIAN P. HERBERT, AR) IS | | REQUIRED. PLEASE REVISE ALL PAGES, BUT ONLY RESUBMIT | | PAGES WHICH CHANGE FOR CODE RELATED COMMENTS. | | | | SHEET 003 G-501 IS NOT DIGITALLY SIGNED. PLEASE CONFIRM | | ALL SHEETS ARE DIGITALLY SIGNED. | | | | 3. SURVEY (004 V-1 BOUNDARY SURVEY) - OK | | | | 4. CIVIL PAGES (ZACHARY D. TODD, PE) - SIGNATURE AND | | TITLE BLOCK ARE OK, BUT SHEET 018 14 WASTEWATER #3 IS | | NOT SIGNED (ALSO SHEET 019, 020; CHECK ALL). | | | | 5. STRUCTURAL PAGES (MURRAY G. BRYNSTESEN, PE) HAS A | | SIGNATURE WHICH DOES NOT APPEAR TO MEET THE | | REQUIREMENTS OF FAC61G15-23.004 (PER EMAIL TO AND FROM | | FBPE). PLESAE CONTACT ME OR WENDY ANDERSON AT FBPE IF | | YOU WISH TO DISCUSS. TITLE BLOCK OK. | | | | 6. MECHANICAL AND PLUMBING PAGES, ENERGY CALCS, | | SYSTEMPS DESIGN REPORT (MIRCEA PELLA, PE) AND | | ELECTRICAL PAGES (LON CARTER, PE) SIGNATURE AND TITLE | | BLOCK OK, BUT LACKS THE LANGUAGE REQUIRED BY | | FAC61G15-23.004 AND LACKS A SEAL (OR SIGNATURE CAN | | STATE "SIGNED AND SEALED"). PLEASE REVISE ALL BUT | | RESUBMIT ONLY PAGES WHICH CHANGE DUE TO CODE RELATED | | COMMENTS. | | |
|