Plan Review Notes
Plan Review Notes For Permit 19040448
Permit Number 19040448
Review Stop R
Sequence Number 1
Notes
Date Text
2019-05-30 08:53:26ROOFING: THE SUBMITTED NOA: 14-0827.18TAMKO MODIFIED
 BITUMEN ROOF SYSTEM OVER STEEL DECK HAS VARIOUS
 SUB-SYSTEMS LISTED WITHIN THE REPORT BUT NONE OF THE
 SUB-SYSTEMS WERE IDENTIFIED AS THE ONE BEING INSTALLED.
 : FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED
 (LIMITATION #7 ALLOWS ENHANCED FASTENING, LIMITATION #
 9 DOESN?T) FOR ROOF ZONES 2 & 3. FASTENER DENSITIES
 SHALL BE INCREASED FOR BOTH INSULATION & THE BASE SHEET
 AS CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT