Plan Review Notes
Plan Review Notes For Permit 19040448
Permit Number 19040448
Review Stop P
Sequence Number 1
Notes
Date Text
2019-05-06 14:32:34PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE OCCUPANT LOAD FOR EACH OCCUPANCY. FBC
 107.3.5
  
 2) SHT. G-101 PLUMBING FIXTURE LIST JANITOR SINKS AS
 (0). PLEASE ADVISED AS FLOOR PLANS SHOWS 2 BEING
 INSTALLED AS REQUIRED IN FBC-P TABLE 403.1
  
 3) TOILET ROOMS 111 AND 209 SHOWS THE CLEAR FLOOR
 SPACES BACKWARDS. PLEASE CORRECT. FBC-ACC 604.3.1,
 606.2
  
 4) PROVIDE CLEAR FLOOR SPACE FOR BOTH DRINKING
 FOUNTAINS ON SHT. A-102, A-104. FBC-ACC 602.2
  
 5) PROVIDE CLEAR FLOOR SPACE AND CABINET HEIGHT DETAIL
 SHOWING MAX HEIGHT TO BE 34" FOR THE BREAK ROOM/
 TRAINING ROOM. FBC-ACC 606.2
  
 6) SHT. A-106 PROVIDE LOCATION ON PLAN SHOWING ROOF
 DRAINS LOCATIONS. FBC 107.2.1
  
 7) SHT. A 401 DOES NOT SHOW ADA GRAB BAR MOUNTING
 HEIGHT. PROVIDE DETAIL SHOWING THAT BAR WILL BE MOUNTED
 33" TO 36" TO THE TOP OF GRIPPING SURFACE. FBC-ACC
 609.4
  
 8) PROVIDE INSTALLATION MANUAL FOR THE OIL/SAND
 INTERCEPTOR SHOWING IT IS LISTED AND LABELED. FBC-P
 1003.4.2
  
 9) PROVIDE CALCULATIONS FOR HOW YOU DETERMINED
 INTERCEPTOR SIZE. FBC-P 1003.4.2.2
  
 10) XA RECESS SUMP PUMP SHALL INDIRECTLY DISCHARGE IN
 TO THE SAND/ OIL INTERCEPTOR. FBC-P 1003.1
  
 11) PROVIDE NOTED ON PLAN THAT BACKFLOWS AND
 INTERCEPTORS REQUIRED THERE OWN SEPERATE PLUMBING
 PERMIT.
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  