2019-05-06 14:32:34 | PLUMBING 1ST REVIEW**DENIED** |
| |
| 1) PROVIDE OCCUPANT LOAD FOR EACH OCCUPANCY. FBC |
| 107.3.5 |
| |
| 2) SHT. G-101 PLUMBING FIXTURE LIST JANITOR SINKS AS |
| (0). PLEASE ADVISED AS FLOOR PLANS SHOWS 2 BEING |
| INSTALLED AS REQUIRED IN FBC-P TABLE 403.1 |
| |
| 3) TOILET ROOMS 111 AND 209 SHOWS THE CLEAR FLOOR |
| SPACES BACKWARDS. PLEASE CORRECT. FBC-ACC 604.3.1, |
| 606.2 |
| |
| 4) PROVIDE CLEAR FLOOR SPACE FOR BOTH DRINKING |
| FOUNTAINS ON SHT. A-102, A-104. FBC-ACC 602.2 |
| |
| 5) PROVIDE CLEAR FLOOR SPACE AND CABINET HEIGHT DETAIL |
| SHOWING MAX HEIGHT TO BE 34" FOR THE BREAK ROOM/ |
| TRAINING ROOM. FBC-ACC 606.2 |
| |
| 6) SHT. A-106 PROVIDE LOCATION ON PLAN SHOWING ROOF |
| DRAINS LOCATIONS. FBC 107.2.1 |
| |
| 7) SHT. A 401 DOES NOT SHOW ADA GRAB BAR MOUNTING |
| HEIGHT. PROVIDE DETAIL SHOWING THAT BAR WILL BE MOUNTED |
| 33" TO 36" TO THE TOP OF GRIPPING SURFACE. FBC-ACC |
| 609.4 |
| |
| 8) PROVIDE INSTALLATION MANUAL FOR THE OIL/SAND |
| INTERCEPTOR SHOWING IT IS LISTED AND LABELED. FBC-P |
| 1003.4.2 |
| |
| 9) PROVIDE CALCULATIONS FOR HOW YOU DETERMINED |
| INTERCEPTOR SIZE. FBC-P 1003.4.2.2 |
| |
| 10) XA RECESS SUMP PUMP SHALL INDIRECTLY DISCHARGE IN |
| TO THE SAND/ OIL INTERCEPTOR. FBC-P 1003.1 |
| |
| 11) PROVIDE NOTED ON PLAN THAT BACKFLOWS AND |
| INTERCEPTORS REQUIRED THERE OWN SEPERATE PLUMBING |
| PERMIT. |
| |
| |
| |