2019-05-10 09:37:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040448
 5/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMISSIONING OF THE MECHANICAL AND SERVICE WATER
 HEATING SYSTEMS IS REQUIRED PER SECTION C408.2 FBC-17
 ENERGY CONSERVATION. SUBMIT A COMMISSIONING PLAN AS
 OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS
 C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY OF THE
 COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT
 FINAL INSPECTION.
  
 2) CLARIFY IF THE FLAMINGO EXHAUST SYSTEM WILL BE
 INSTALLED UNDER A SEPARATE PERMIT. CURRENTLY THERE ARE
 NO PLANS AND SPECIFICATIONS SUBMITTED EXCEPT FOR THE
 EXHAUST FAN- SECTION 107.2.1 WPB.
  
 3) SHEET M2.1: AN EXHAUST VENTILATION SYSTEM IS
 REQUIRED FOR THE CAR SERVICE RECEPTION ROOM IN
 COMPLIANCE WITH TABLE 403.3.1.1 AND SECTION 404 FBC M.
 THE ROOM HAVING AN OPENING ON ONLY ONE SIDE DOES NOT
 MEET THE REQUIREMENT OF HAVING OPENINGS ON TWO OR MORE
 SIDES- SEE SECTIONS 406.5, 406.5.2, AND 406.6 FBC B AND
 REVISE THE PLANS AND EXHAUST CALCULATIONS IN THE TABLE
 ON SHEET M0.1:
  
 4) SHEET M2.1 & M2.2: AN EXHAUST VENTILATION SYSTEM IS
 REQUIRED FOR THE CAR SHOWROOM IN COMPLIANCE WITH TABLE
 403.3.1.1 AND SECTION 404 FBC M. ALTHOUGH THE SHOWROOM
 IS CLASSIFIED AS A BUSINESS OCCUPANCY PER SECTION 304.1
 FBC B, MOTOR VEHICLES WILL BE PARKED IN THE ROOM, AND
 THE ROOM IS OPEN TO THE PUBLIC. REVISE THE PLANS, AND
 EXHAUST CALCULATIONS IN THE TABLE ON SHEET M0.1:
  
 5) M2.1 RECIRCULATION OF AIR FROM THE SERVICE ROOM INTO
 THE LOCKER ROOM IS PROHIBITED PER TABLE 403.3.1.1
 FOOTNOTE B.
  
 6) M2.1 & M2.2: AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS ARE REQUIRED FOR THE O/A DUCTS AT EACH AIR
 HANDLER LOCATION - SECTION C403.2.4.3 FBC EC.
  
 7) M2.1 & M2.2: PLEASE SHOW THE FLEX DUCT SIZES-
 SECTION 603.2 FBC M.
  
 8) M2.2 & M2.3: PROVIDE CLEARANCE DISTANCE MEASUREMENTS
 FOR THE RTU?S AND ROOF FANS TO THE ROOF EDGES- SECTION
 304.11 FBC M.
  
 9) M2.2 & M2.3: PROVIDE CLEARANCE DISTANCE MEASUREMENTS
 FOR MECHANICAL AND GRAVITY AIR INTAKES TO EXHAUST AIR
 OUTLETS- SECTION 401.4 FBC M.
  
 10) M2.2, M2.3, & M7.1: PROVIDE COMPLETE WIND LOAD
 ENGINEERING FOR INSTALLATION OF THE RTU'S, ROOFTOP
 CONDENSERS AND STANDS, ROOFTOP FANS AND CURBS, AND
 GRAVITY VENTILATORS. PLEASE INCLUDE THE DESIGN
 CRITERIA- SECTION 1609 FBC B, AND SECTION 301.15 FBC M,
 AND FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S FOR
 AC ROOF STANDS AND FAN CURBS.
  
 11) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AC
 SYSTEMS INCLUDING TYPE AND SIZES OF CONDENSATE PIPING,
 PIPING RUNS, PIPING SUPPORTS INSIDE AND ABOVE THE ROOF,
 AND DISCHARGE LOCATIONS- SEE SECTION 307.2 FBC M.
  
 12) PROVIDE INSTALLATION DETAILS FOR THE CIRCULATION
 FANS IN THE SERVICE AND SERVICE RECEPTION AREAS-
 SECTION 107.2.1 WPB, AND SECTION 304.1 FBC M.
  
 13) EMERGENCY GENERATOR: A) SHOW THE LOCATION ON THE
 MECHANICAL PLANS WITH ALL REQUIRED CLEARANCE DISTANCE
 MEASUREMENTS. B) SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE GENERATOR, EXHAUST AND FUEL OIL PIPING. C)
 SUBMIT THE UL 2200 CERTIFICATE FOR THE GENERATOR. D)
 PROVIDE AN ENLARGED DRAWING SHOWING THE EXHAUST FLUE
 RUN AND TERMINATION LOCATION, AND THE FUEL OIL PIPING
 RUN AND SOURCE LOCATION. E) PROVIDE WIND LOAD
 ENGINEERING FOR INSTALLATION OF THE GENERATOR AND ALL
 ASSOCIATED EXTERIOR EQUIPMENT- SECTION 301.15 FBC M.
 REFERENCES: SECTION 915.1 FBC M, SECTIONS 4.1, 6.1, &
 8.1 NFPA 37, SECTION 4.1 NFPA 110.
  
 14) PLEASE PROVIDE AN ENLARGED COMPRESSOR ROOM PLAN AND
 EQUIPMENT SCHEDULE. IT APPEARS THAT FUEL OIL TANKS WILL
 BE INSTALLED IN THE ROOM WHICH REQUIRES THE ROOM, THE
 TANK INSTALLATION, AND VENTILATION SYSTEM TO BE IN
 COMPLIANCE WITH NFPA 30. A) PLEASE SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR THE TANKS. B) PROVIDE
 THE CLASSIFICATION OF THE FUEL AND SUBMIT AN MSDS
 SHEET- SECTION 4.3.1. C) PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR EF-4 AND INDICATE THE SEQUENCE OF
 OPERATION- SECTION 24.10.1 NFPA 30, AND SECTION 510.2
 FBC M.
  
 15) REQUIRED SUBMITTALS LISTED BELOW SHALL BE PROVIDED
 WITH THE CORRECTED PLANS OR MAY BE DEFERRED BY REQUEST.
 ALL SUBMITTALS SHALL BEAR THE SHOP DRAWING APPROVAL
 STAMP BY THE ENGINEER OF RECORD.
  
 1) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR
 INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT (AS
 NOTED ABOVE IN COMMENT #10).
 2) C0, N02, CO2, FV SENSORS AND CONTROLLERS.
 3) MOTORIZED DAMPERS.
 4) DUCT SMOKE DETECTORS.
 5) FIRE DAMPERS
 6) GENERATOR
 7) FUEL OIL TANKS
 8) AIR COMPRESSOR
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  