Plan Review Notes
Plan Review Notes For Permit 19040448
Permit Number 19040448
Review Stop E
Sequence Number 1
Notes
Date Text
2019-05-09 12:28:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED LOAD CALCULATION FOR SIZING THE SERVIE
  
 2) NEED LOAD CALCULATION FOR SIZING THE GENERATOR
  
 3) NEED LOAD CALCULATION FOR THE ATS
  
 4) ATS WILL HAVE TO MEET THE REQUIREMENTS ON 240.87
  
 240.87 ARC ENERGY REDUCTION
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE
 ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT
 BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL
 APPLY