Plan Review Notes
Plan Review Notes For Permit 19040448
Permit Number 19040448
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-30 09:06:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040448
 ADD: 2700 S AUSTRALIAN AVE.
 CONT: AUTOBUILDERS GENERAL CONT. SVCS. INC.
 TEL: 561-622-3515
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 29/2019
 ACTION: DENIED
  
 1) SHEET 002-G-101 THE LIFE SAFETY PLAN:
 1A). UNDER THE HEADING BUILDING CODE SUMMARY THE
 PROPOSED USE IS LISTED AS BUSINESS (B) AND STORAGE
 (S1). PLEASE NOTE THAT THE SERVICE SHOP IS LISTED AS A
 S1 OCCUPANCY. FOR MOTOR VEHICLE REPAIR GARAGES
 COMPLYING WITH THE MAXIMUM ALLOWABLE QUANTITIES OF
 HAZARDOUS MATERIALS LISTED IN TABLE 307.1(1).
 PLEASE SUBMIT A LIST OF HAZARDOUS MATERIALS AND
 ALLOWABLE QUANTITIES PER THE 2017 FBC-B TABLE 307.1(1).
  
 1B) UNDER THE HEADING OF BUILDING DATA THE PLANS ARE
 INDICATED THEY ARE DESIGNED UNDER THE 2014 FBC. PLEASE
 NOTE THAT THE 2017 FBC-B WAS ADOPTED STATEWIDE ON DEC.
 31/ 2017. PLEASE UPDATE PLANS.
  
 1C) UNDER THE BUILDING DATA THERE IS NO LISTING FOR THE
 REQUIRED AREA OF REFUGE, THIS IS A 2 STORY BUILDING AND
 NO FIRE SPRINKLERS. THE 2017 FBC-ACCESSIBILITY CODE
 UNDER SECTION 207 ACCESSIBLE MEANS OF EGRESS. SECTION
 207.1. MEANS OF EGRESS SHALL COMPLY WITH SECTION 1007
 OF THE INTERNATIONAL BUILDING CODE (2003 EDITION).
 PLEASE REVIEW IN THE 2003 IBC-B SECTIONS DEALING WITH:
 1007.3 ENCLOSED EXIT STAIRWAYS, 48 INCHES BETWEEN
 HANDRAILS.
 1007.4 ELEVATORS.
 1007.6 AREAS OF REFUGE.
 1007.6.1. SIZE.
 1007.6.2. SEPARATION.
 1007.6.3. TWO-WAY COMMUNICATION.
 1007.6.4. INSTRUCTIONS.
 1007.6.5. IDENTIFICATION.
 1007.7.7. SIGNAGE.
  
 1D) SEPARATED MIXED OCCUPANCY SHOWS THE FORMULA FOR
 AREA CALCULATIONS BUT HAS LEFT THE CALCULATION BLANK.
 PLEASE PROVIDE THE ACTUAL AND ALLOWABLE SQUARE FEET FOR
 EACH OF THE OCCUPANCIES AND THE END CALCULATION. 2017
 FBC-B 508.3.3.
  
 1E) PLEASE NOTE THE PLANS DOES NOT STATE THE ACTUAL
 OCCUPANT LOAD FOR EACH OF THE OCCUPANCIES. THE EXIT
 WIDTH DOES PROVIDE THE AREA FOR EACH OCCUPANCY AND AREA
 PER OCCUPANT (TABLE 1004.1.2) BUT DOES NOT GIVE THE
 ACTUAL OCCUPANT LOAD PER STORY AND THE TOTAL OCCUPANT
 LOAD. 2017 FBC-B 1004.1 & TABLE 1004.1.2.
  
 1F) THE LIFE SAFETY SHEET 002-G-101 UNDER THE HEADING
 OF ALLOWABLE AREA, MIXED OCCUPANCY INDICATES YES, AND
 SEPARATION 2 HRS. THE FIRST FLOOR PARTS ROOM HAS A NOTE
 2 HRS. IT WOULD APPEAR THAT THIS NOTE REFERS TO THE
 BLOCK WALL BETWEEN THE BUSINESS OCCUPANCY AND S1 REPAIR
 GARAGE. THE FIRST FLOOR PLAN SHEET 041-A-101 HAS THIS
 SAME WALL WITH A WALL IDENTIFICATION TAG IDENTIFIED AS
 WALL TYPE 10. SHEET 042-A-102 THE SECOND FLOOR HAS THE
 SAME WALL TYPE IDENTIFIED WITH A WALL IDENTIFICATION
 TAG AS WALL TYPE 6. WHEN YOU OPEN UP SHEET 050-A-501
 WALL TYPES NONE OF THE WALL TYPES SHOWN HAVE THE SAME
 NAMING CONVENTION.
  
 1G) SHEET A-501 WALL TYPES A3-A6 ALL SHOW BLOCK WALLS
 WITH EITHER 8 INCH OR 12 INCH CMU. INFORMATION ON THE
 PLANS HAS TO BE SPECIFIC NO EITHER, OR. SUCH DRAWINGS
 AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE
 FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 1H) PLEASE NOTE THE DESIGNER OF RECORD CAN DESIGN TO A
 MORE STRINGENT STANDARD, BUT UNDER THE 2017
 FBC-B TABLE 508.4 THERE IS NO OCCUPANCY SEPARATION
 REQUIRED BETWEEN A B AND S1 OCCUPANCY. IF THERE IS A
 DIFFERENCE BETWEEN THE FIRE CODE AND BUILDING CODE THEN
 THE MOST STRINGENT CODE PREVAILS.
  
 1I) THE LIFE SAFETY SHEET 002-G-101 SHOWS A SECOND
 STORY BUSINESS AND STORAGE OCCUPANCY,
 (ASSUMED S-1). THE TRAVEL DISTANCE IS SHOWN GOING DOWN
 THROUGH THE STAIRWAY MAKING THIS STAIRWAY EXIT ACCESS
 AND THE TRAVEL DISTANCE ON THE STAIRS TO BE TAKEN
 PARALLEL TO THE STAIRS. FROM THE FURTHEST POINT TAKEN
 ON THE SECOND FLOOR TO THE FIRST FLOOR LANDING THE
 TRAVEL DISTANCE IS BETWEEN 85 TO 90 FEET. THIS IS OVER
 THE ALLOWABLE MAXIMUM COMMON PATH OF TRAVEL FROM TABLE
 1006.3.2(2) OF 75 FEET AND OCCUPANT LOAD OF 49 FOR
 BUSINESS OR 29 FOR STORAGE OCCUPANCY. IF THE STAIRWAY
 WAS A RATED 1 HOUR EXIT STAIRWAY WITH OPENING
 PROTECTIVES AND EXIT PASSAGEWAY TO THE EXTERIOR, THEN
 THE TRAVEL DISTANCE FOR THE 2ND FLOOR WOULD WORK.
 PLEASE REVIEW ALL OF THE REQUIREMENTS FOR EXIT AND EXIT
 PASSAGEWAYS. EXIT PASSAGEWAYS ARE FOUND UNDER FBC-B
 1024. PLEASE REVIEW VENTILATION REQUIREMENTS (FBC-B
 1024.7) FOR EXIT PASSAGEWAYS AS WELL.
  
 1J) STAIRWAY GUARDRAIL. SHEET 049-A-101. PLEASE PROVIDE
 A DETAIL SHOWING COMPLIANCE WITH:
 2017 FBC-B 1015.4 OPENING LIMITATIONS. REQUIRED GUARDS
 SHALL NOT HAVE OPENINGS THAT ALLOW PASSAGE OF A SPHERE
 4 INCHES (102 MM) IN DIAMETER FROM THE WALKING SURFACE
 TO THE REQUIRED GUARD HEIGHT.
  
 2A) SHEET 042-A102 THE 2ND FLOOR PLAN AND ROOF PLAN OF
 THE REPAIR GARAGE, SHOWS A ROOF HATCH TO GAIN ACCESS TO
 THE MECHANICAL EQUIPMENT ON THE ROOF. SHEET 047-A-301
 SHOWS A VERTICAL DISTANCE FROM THE FINISH FLOOR TO THE
 BOTTOM OF THE BAR JOIST OF 14.66 FEET, CENTERED IN THE
 SERVICE BAY DOORWAY. THE VERTICAL DISTANCE FROM FINISH
 FLOOR TO THE TOP OF THE ROOF AT THE ROOF HATCH IS OVER
 18.50 FEET. PLEASE SHOW HOW COMPLIANCE WITH 306.5 OF
 THE 2017 MECHANICAL CODE WILL BE MET:
 2017 FBC-MECHANICAL. 306.5 EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE
 LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A
 BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER
 THAN 16 FEET (4877 MM) ABOVE GRADE TO ACCESS SUCH
 EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS
 OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) IN HEIGHT.
  
 2B) 2017 FBC-B 1015.6 MECHANICAL EQUIPMENT. GUARDS
 SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS,
 ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE
 SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF
 EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR
 OPEN SIDE IS LOCATED MORE THAN 30 INCHES ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES IN DIAMETER. THE GUARD SHALL EXTEND NOT LESS
 THAN 30 INCHES BEYOND EACH END OF SUCH APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT.
  
 2C) PLEASE ALSO PROVIDE CODE COMPLIANCE WITH: 2017
 FBC-B ROOF HATCH EXCEPTION: IN BUILDINGS WITHOUT AN
 OCCUPIED ROOF, ACCESS TO THE ROOF SHALL BE PERMITTED TO
 BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE
 FEET IN AREA AND HAVING A MINIMUM DIMENSION OF 2 FEET.
  
 3) SHEET 028-S-1.0. EARTHWORK GENERAL NOTES: NOTE # 1
 INDICATES ALL EARTHWORK SHALL BE DONE IN ACCORDANCE
 WITH THE REQUIREMENTS OUTLINED IN THE GEOTECHNICAL
 REPORT BY XXXXXXX/ DATE: XXXXX, MINIMUM BEARING
 PRESSURE XXXXXXX. PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 4) SHEET 029-S-1.1 PROVIDES THE WIND PRESSURES (VASD)
 FOR WALL ZONES 4 & 5 BUT THERE ARE NO PRESSURES FOR
 ROOF ZONES 1, 2 OR 3. 2017 FBC-B 1603.1.4. WIND DESIGN
 DATA.
  
 5) THIS BUILDING HAS WELDED AND BOLTED STEEL
 CONNECTIONS, PLEASE PROVIDE COMPLIANCE WITH, THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 6) THE SUBMITTED NOA: 14-0827.18TAMKO MODIFIED BITUMEN
 ROOF SYSTEM OVER STEEL DECK HAS VARIOUS SUB-SYSTEMS
 LISTED WITHIN THE REPORT BUT NONE OF THE SUB-SYSTEMS
 WERE IDENTIFIED AS THE ONE BEING INSTALLED. : FOR ALL
 ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED
 (LIMITATION #7 ALLOWS ENHANCED FASTENING, LIMITATION #
 9 DOESN?T) FOR ROOF ZONES 2 & 3. FASTENER DENSITIES
 SHALL BE INCREASED FOR BOTH INSULATION & THE BASE SHEET
 AS CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 7) THE SUBMITTAL NOA: 16-0219.01 TC-5SERIES STEEL ROOF
 CURB FOR TRANE ROOF TOP UNITS. PLEASE REVIEW SHEET 4
 AND 5 OF THE PRODUCT APPROVAL FOR TECHNICAL NOTES.
 RESTRAINT BRACKET QUANTITY IS DETERMINED BY PROJECT
 SPECIFIC CALCULATIONS, PERFORMED BY A FLORIDA LICENSED
 PE OR FLORIDA REGISTERED ARCHITECT THAT CONSIDER THE
 UNIQUE COMBINATION OF THE UNIT SIZE AND APPLICABLE
 LATERAL AND UPLIFT PRESSURES FOR EACH JOB. PLEASE
 PROVIDE CALCULATION FOR HOW MANY BRACKETS WILL BE
 NEEDED FOR EACH TYPE OF UNIT. 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED. 2017 FBC-M- 301.15 WIND
 RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 8) THE SUBMITTAL NOA: 17-1017.14 TRULITE SERIES 3100
 REGISTER ALUMINUM STOREFRONT/ WINDOW WALL SYSTEM- L. M.
 I. SHEETS 2-5 DO NOT OPEN FOR REVIEW. PLEASE NOTE ON
 PAGE 6 ONLY THE BOTTOM SERIES OF GLASS IS HIGHLIGHTED
 FOR PRESSURES. THE UPPER WINDOW GLASS IS NOT MENTIONED.
 THE UPPER GLAZING UNITS WHICH HAVE BOTH VERTICAL AND
 HORIZONTAL FRAMING MEMBERS ARE NOT IDENTIFIED ON SHEETS
 8 AND 9 OF THE REPORT NOR IS THE CHART HIGHLIGHTED OR
 CIRCLED TO IF THE JAMBS ARE REQUIRED TO BE STEEL
 RE-ENFORCED. SHEET 10 OF 17 THE DOOR MULLION INDICATES
 TRULITE DOORS ARE UNDER A SEPARATE NOA. SHEET 13 OF 17
 THE ANCHOR LOAD CHART IS NOT IDENTIFIED AS TO THE TYPE
 OF ANCHOR FOR THE FRAME WIDTH AND HEIGHT.
 IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 9) GENSTEEL SERIES GENSTORM OUTSWING DOOR NOA:
 17-0803.01 PLEASE PROVIDE THE TYPE OF LOCK OPTION THAT
 WILL BE USED WITH THIS DOOR. SEE SHEET 9 OF 11.
  
 10) THE SUBMITTAL NOA: 17-1218.02 MIAMI TECH ALUMINUM
 A/C STAND. THE ROOF TOP A/C STAND PRODUCT APPROVAL A
 MIAMI-DADE NOA # 17-1218.02 WAS SUBMITTED, REVIEWED BY
 THE DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING
 REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE
 ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN
 ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS
 AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND
 THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT.
  
 11) THE PERMIT APPLICATION INDICATES THAT THE SQUARE
 FOOTAGE OF THE AUTO DEALERSHIP BEING 15,805 SQ. FT.
 THAT WOULD APPEAR TO BE THE 1ST FLOOR ONLY. THE TOTAL
 SQ. FOOTAGE I CALCULATED WAS 18,534.00 SQ. FT.
 DISCREPANCY IN SQ. FT.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 12) INFORMATION REQUIRED, SINCE THIS PROJECT IS A NEW
 AUTOMOBILE DEALERSHIP WILL THEY BE FILLING THE CARS
 WITH GASOLINE? I DIDN'T SEE TANKS ON ANY PLAN, ARE THEY
 TO BE ABOVE GROUND OR BENEATH THE GROUND? NOTE
 PETROLEUM TANKS ARE TO BE REVIEWED UNDER SEPARATE
 PERMIT, FEES AND REVIEWS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 13) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 14) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  