Plan Review Notes
Plan Review Notes For Permit 19040349
Permit Number 19040349
Review Stop M
Sequence Number 1
Notes
Date Text
2019-04-10 16:18:521ST REVIEW FBC-2017 MECHANICAL
 REVISION #19040349
 MASTER #19021148
 4/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DRESSING ROOMS FOR RETAILL STORES (NOT ASSOCIATED
 WITH LOCKER ROOMS) REQUIRE EXHAUST VENTILATION AT A
 RATE OF 0.25 CFMS PER SF- SEE TABLE 403.3.1.1 FBC M.
 THERE IS NO EXCEPTION SHOWN IN THE TABLE FOR DRESSING
 ROOMS WITHOUT CEILINGS OR DOORS. PLEASE PROVIDE THE
 EXHAUST FANS THAT WERE SHOWN ON THE ORIGINAL APPROVED
 PLAN, AND SHOW THE EXHAUST DUCT RUNS AND TERMINATION
 LOCATIONS.
  
 2) PLEASE PROVIDE THE TYPE AND SIZE OF DIFFUSERS FOR
 THE NEW 8" DUCT DROPS- SECTION 603 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  