2019-08-20 17:42:04 | GOOD AFTERNOON DAVID, |
| |
| I DISCUSSED YOUR QUESTIONS WITH ROBERT BROWN (BUILDING |
| OFFICIAL) AND GEORGE JOHNSON (PLUMBING PLAN REVIEWER) |
| BEFORE REPLYING TO YOUR E-MAIL. |
| |
| 1) THE PROPOSED KITCHEN FALLS MORE INTO THE U SHAPE |
| KITCHEN THAT IS ENCLOSED ON THREE CONTIGUOUS SIDES. THE |
| 60 INCHES TURN AROUND INSIDE THE KITCHEN WORK AREAS IS |
| REQUIRED. ROBERT SUGGESTED THAT MAY BE BY PROVIDING THE |
| 60 INCHES IN THE ISLE BETWEEN THE TRIPLE SINK |
| COMPARTMENT AND THE ISLAND COUNTER WILL PROVIDE THE |
| REQUIRED TURNING SPACE. |
| |
| 2) YOU ARE RIGHT THIS IS NOT A RESIDENTIAL DWELLING |
| UNIT. THE KITCHEN WORK SURFACE IS REQUIRED FOR ALL |
| KITCHENS. SEC. 804.3.1 IS NOT REFERRING TO "RESIDENTIAL |
| DWELLING UNITS". SECTION 804.3 MENTIONS RESIDENTIAL |
| DWELLING UNITS TO CLARIFY THAT RESIDENTIAL UNITS NEED |
| TO HAVE AT LEAST 30 INCHES WIDE MINIMUM SECTION OF |
| COUNTER PROVIDING THE KITCHEN WORK SURFACE COMPLYING |
| WITH ALL THE REQUIREMENTS OF SEC. 804.3. |
| |
| 3) REGARDING THE MICROWAVE, IF YOU PROVIDE THE |
| COUNTERTOP TYPE MICROWAVE, THEN THE MICROWAVE ABOVE THE |
| COOKTOP IS NOT EQUIVALENT. IF THE COUNTER MICROWAVE |
| FAILS , THEN THE OTHER DOESN'T COMPLY. THEREFORE, THE |
| ANSWER IS NO. |
| |
| 4) REGARDING THE SINK. IT WILL NEED TO COMPLY WITH THE |
| FRONT APPROACH AND REQUIRED HEIGHT. THIS SINK IS FOR |
| PUBLIC USE AN ACCOMMODATION. PLEASE COORDINATE WITH |
| GEORGE JOHNSON (PLUMBING PLAN EXAMINER). SEE CONTACT |
| INFORMATION BELOW. BY THE WAY, PLUMBING PLANS NEED TO |
| BE REVISED ALSO. PLUMBING HAVE NOT SEEN THE PROPOSED |
| REVISIONS. THIS MAY AFFECT THE PLUMBING INSPECTIONS IF |
| PLANS DON'T MATCH WORK IN THE FIELD. |
| |
| |
| GEORGE PRIEST JOHNSON |
| PLUMBING PLANS EXAMINER II |
| DEVELOPMENT SERVICES |
| BUILDING INSPECTIONS |
| |
| PHONE: 805-6700 EXT: 6711 |
| FAX: 805-6676 |
| E-MAIL: [email protected] |
| |
| |
| PLEASE FEEL FREE TO CALL ME IF YOU HAVE ANY QUESTIONS, |
| THANK YOU |
| |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |
| -----ORIGINAL MESSAGE----- |
| FROM: DAVID |
| SENT: TUESDAY, AUGUST 20, 2019 9:29 AM |
| TO: JULIO GOMEZ ; [email protected] |
| SUBJECT: 1803 AUSTRALIAN |
| |
| GOOD MORNING JULIO, |
| |
| RE: 19040288 |
| |
| THANK YOU FOR GETTING BACK TO AMMI AND I SO QUICKLY |
| WITH YOUR COMMENTS. I HAVE A COUPLE OF QUESTIONS |
| THOUGH: |
| |
| 1) I THOUGHT OUR KITCHENETTE WAS A PASSTHROUGH TYPE NOT |
| A "U" SHAPE. WE HAVE TWO ENTRANCES/EXITS INTO THE SPACE |
| NOT A DEAD END SITUATION WHERE A TURNAROUND WOULD BE |
| NECESSARY. |
| |
| 2) SEC 804.3.1 FBCA IS REFERRING TO "RESIDENTIAL |
| DWELLING UNITS" WHICH WE ARE CERTAINLY NOT. THIS IS |
| MORE OF A CONTINENTAL BREAKFAST TYPE SETUP, OR A GRAB N |
| GO. |
| |
| 3) IF WE WERE TO HAVE AN ADDITIONAL COUNTERTOP TYPE |
| MICROWAVE THAT MEETS REACH REQUIREMENTS CAN WE KEEP THE |
| MICROWAVE ABOVE THE COOKTOP? |
| |
| 4) I UNDERSTAND THE KITCHEN SINK HEIGHT REQUIREMENT OF |
| 34", HOWEVER THE THREE COMPARTMENT SINK IS FOR |
| EMPLOYEES DOING SANITARY WASHING. IS THERE ANY WAY YOU |
| CAN APPROVE A PARALLEL APPROACH OF 36" HIGH BECAUSE |
| THIS IS A "SERVICE STYLE" COUNTER OR A "FOOD SERVICE |
| LINE" COUNTER? |
| |
| THANK YOU FOR YOUR ATTENTION TO THIS MATTER. |
| |
| SINCERELY, |
| |
| DAVID J. GENGLER, A.I.A |
| (561) 340-9320 |
| |
| |
| ****ORIGINAL COMMENTS: |
| |
| REVISION, SECOND BUILDING REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 1- ARCHITECT STATES ON SHEET A-02 THAT "THIS KITCHEN |
| SHALL BE USED AS A DOMESTIC KITCHEN FOR USE BY |
| INDIVIDUAL PATIENTS & GUESTS AS WELL AS FOR THE |
| PURPOSES OF STORING AND HEATING FOOD PREPARED OFFSITE. |
| NO FOOD SHALL BE PREPARED FOR PUBLIC CONSUMPTION IN |
| THIS KITCHEN". |
| |
| A)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| KITCHEN COMPLIANCE WITH SEC. 804 FBC-ACCESSIBILITY AS |
| REQUIRED BY SEC. 212 FBC-ACCESSIBILITY. |
| |
| RESPONSE: |
| (1) SEC. 804.2.2 FBC-ACCESSIBILITY FOR U-SHAPED |
| KITCHENS REQUIRES 60" CLEARANCE BETWEEN ALL OPPOSING |
| BASE CABINETS, COUNTER TOPS, APPLIANCES OR WALL WITHIN |
| KITCHEN WORK AREAS. PLEASE REVISE PLANS AS REQUIRED. |
| |
| (2) PLEASE SHOW THE KITCHEN WORK SURFACE POSITIONED FOR |
| A FORWARD APPROACH AS REQUIRED BY SEC. 804.3.1 |
| FBC-ACCESSIBILITY. ALSO, SHOW KNEE AND TOE CLEARANCE |
| COMPLYING WITH SEC. 306 FBC-ACCESSIBILITY. AND SPECIFY |
| THE HEIGHT OF THE KITCHEN WORK SURFACE AS REQUIRED BY |
| SEC. 804.3.2 FBC-ACCESSIBILITY |
| |
| (3) THE LOCATION OF THE MICROWAVE ABOVE THE COOKTOP |
| DOESN'T SEEM TO COMPLY WITH SEC. 308.3.2 |
| FBC-ACCESSIBILITY FOR SIDE REACH WITH AN OBSTRUCTION. |
| PLEASE, REVISE AS REQUIRED. |
| |
| (4) PROVIDE INFORMATION SHOWING THE HEIGHT OF THE SINK |
| AS REQUIRED BY SEC. 804.4 AND SEC. 606.3 |
| FBC-ACCESSIBILITY |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |