2019-08-19 18:09:46 | REVISION, SECOND BUILDING REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 1- ARCHITECT STATES ON SHEET A-02 THAT "THIS KITCHEN |
| SHALL BE USED AS A DOMESTIC KITCHEN FOR USE BY |
| INDIVIDUAL PATIENTS & GUESTS AS WELL AS FOR THE |
| PURPOSES OF STORING AND HEATING FOOD PREPARED OFFSITE. |
| NO FOOD SHALL BE PREPARED FOR PUBLIC CONSUMPTION IN |
| THIS KITCHEN". |
| |
| A)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| KITCHEN COMPLIANCE WITH SEC. 804 FBC-ACCESSIBILITY AS |
| REQUIRED BY SEC. 212 FBC-ACCESSIBILITY. |
| |
| RESPONSE: |
| (1) SEC. 804.2.2 FBC-ACCESSIBILITY FOR U-SHAPED |
| KITCHENS REQUIRES 60" CLEARANCE BETWEEN ALL OPPOSING |
| BASE CABINETS, COUNTER TOPS, APPLIANCES OR WALL WITHIN |
| KITCHEN WORK AREAS. PLEASE REVISE PLANS AS REQUIRED. |
| |
| (2) PLEASE SHOW THE KITCHEN WORK SURFACE POSITIONED FOR |
| A FORWARD APPROACH AS REQUIRED BY SEC. 804.3.1 |
| FBC-ACCESSIBILITY. ALSO, SHOW KNEE AND TOE CLEARANCE |
| COMPLYING WITH SEC. 306 FBC-ACCESSIBILITY. AND SPECIFY |
| THE HEIGHT OF THE KITCHEN WORK SURFACE AS REQUIRED BY |
| SEC. 804.3.2 FBC-ACCESSIBILITY |
| |
| (3) THE LOCATION OF THE MICROWAVE ABOVE THE COOKTOP |
| DOESN'T SEEM TO COMPLY WITH SEC. 308.3.2 |
| FBC-ACCESSIBILITY FOR SIDE REACH WITH AN OBSTRUCTION. |
| PLEASE, REVISE AS REQUIRED. |
| |
| (4) PROVIDE INFORMATION SHOWING THE HEIGHT OF THE SINK |
| AS REQUIRED BY SEC. 804.4 AND SEC. 606.3 |
| FBC-ACCESSIBILITY |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |