Date |
Text |
2019-06-14 08:41:42 | REVISION, BUILDING REVIEW COMMENTS |
| CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. |
| |
| 1- ARCHITECT STATES ON SHEET A-02 THAT "THIS KITCHEN |
| SHALL BE USED AS A DOMESTIC KITCHEN FOR USE BY |
| INDIVIDUAL PATIENTS & GUESTS AS WELL AS FOR THE |
| PURPOSES OF STORING AND HEATING FOOD PREPARED OFFSITE. |
| NO FOOD SHALL BE PREPARED FOR PUBLIC CONSUMPTION IN |
| THIS KITCHEN". |
| |
| A)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| KITCHEN COMPLIANCE WITH SEC. 804 FBC-ACCESSIBILITY AS |
| REQUIRED BY SEC. 212 FBC-ACCESSIBILITY. |
| |
| B) SHOW ON PLANS HOW COMPLYING WITH ALL THE |
| REQUIREMENTS OF SEC. 407.2.6 FBC-BUILDING. |
| |
| SEC. 407.2.6 NURSING HOME COOKING FACILITIES. |
| IN GROUP I-2, CONDITION 1, OCCUPANCIES, ROOMS OR SPACES |
| THAT CONTAIN A COOKING FACILITY WITH DOMESTIC COOKING |
| APPLIANCES SHALL BE PERMITTED TO BE OPEN TO THE |
| CORRIDOR WHERE ALL OF THE FOLLOWING CRITERIA ARE MET: |
| |
| 1.THE NUMBER OF CARE RECIPIENTS HOUSED IN THE SMOKE |
| COMPARTMENT IS NOT GREATER THAN 30. |
| |
| 2.THE NUMBER OF CARE RECIPIENTS SERVED BY THE COOKING |
| FACILITY IS NOT GREATER THAN 30. |
| |
| 3.ONLY ONE COOKING FACILITY AREA IS PERMITTED IN A |
| SMOKE COMPARTMENT. |
| |
| 4.THE TYPES OF DOMESTIC COOKING APPLIANCES PERMITTED |
| ARE LIMITED TO OVENS, COOKTOPS, RANGES, WARMERS AND |
| MICROWAVES. |
| |
| 5.THE CORRIDOR IS A CLEARLY IDENTIFIED SPACE DELINEATED |
| BY CONSTRUCTION OR FLOOR PATTERN, MATERIAL OR COLOR. |
| |
| 6.THE SPACE CONTAINING THE DOMESTIC COOKING FACILITY |
| SHALL BE ARRANGED SO AS NOT TO OBSTRUCT ACCESS TO THE |
| REQUIRED EXIT. |
| |
| 7.A DOMESTIC COOKING HOOD INSTALLED AND CONSTRUCTED IN |
| ACCORDANCE WITH SECTION 505 OF THE FLORIDA BUILDING |
| CODE, MECHANICAL IS PROVIDED OVER THE COOKTOP OR RANGE. |
| |
| 8.THE DOMESTIC COOKING HOOD PROVIDED OVER THE COOKTOP |
| OR RANGE SHALL BE EQUIPPED WITH AN AUTOMATIC |
| FIRE-EXTINGUISHING SYSTEM OF A TYPE RECOGNIZED FOR |
| PROTECTION OF DOMESTIC COOKING EQUIPMENT. PREENGINEERED |
| AUTOMATIC EXTINGUISHING SYSTEMS SHALL BE TESTED IN |
| ACCORDANCE WITH UL 300A AND LISTED AND LABELED FOR THE |
| INTENDED APPLICATION. THE SYSTEM SHALL BE INSTALLED IN |
| ACCORDANCE WITH THIS CODE, ITS LISTING AND THE |
| MANUFACTURER'S INSTRUCTIONS. |
| |
| 9.A MANUAL ACTUATION DEVICE FOR THE HOOD SUPPRESSION |
| SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH SECTIONS |
| 904.12.1 AND 904.12.2. |
| |
| 10.AN INTERLOCK DEVICE SHALL BE PROVIDED SUCH THAT UPON |
| ACTIVATION OF THE HOOD SUPPRESSION SYSTEM, THE POWER OR |
| FUEL SUPPLY TO THE COOKTOP OR RANGE WILL BE TURNED OFF. |
| |
| 11.A SHUT-OFF FOR THE FUEL AND ELECTRICAL POWER SUPPLY |
| TO THE COOKING EQUIPMENT SHALL BE PROVIDED IN A |
| LOCATION THAT IS ACCESSIBLE ONLY TO STAFF. |
| |
| 12.A TIMER SHALL BE PROVIDED THAT AUTOMATICALLY |
| DEACTIVATES THE COOKING APPLIANCES WITHIN A PERIOD OF |
| NOT MORE THAN 120 MINUTES. |
| |
| 13.A PORTABLE FIRE EXTINGUISHER SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |