Plan Review Notes
Plan Review Notes For Permit 19040288
Permit Number 19040288
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-14 08:41:42REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 1- ARCHITECT STATES ON SHEET A-02 THAT "THIS KITCHEN
 SHALL BE USED AS A DOMESTIC KITCHEN FOR USE BY
 INDIVIDUAL PATIENTS & GUESTS AS WELL AS FOR THE
 PURPOSES OF STORING AND HEATING FOOD PREPARED OFFSITE.
 NO FOOD SHALL BE PREPARED FOR PUBLIC CONSUMPTION IN
 THIS KITCHEN".
  
 A)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 KITCHEN COMPLIANCE WITH SEC. 804 FBC-ACCESSIBILITY AS
 REQUIRED BY SEC. 212 FBC-ACCESSIBILITY.
  
 B) SHOW ON PLANS HOW COMPLYING WITH ALL THE
 REQUIREMENTS OF SEC. 407.2.6 FBC-BUILDING.
  
 SEC. 407.2.6 NURSING HOME COOKING FACILITIES.
 IN GROUP I-2, CONDITION 1, OCCUPANCIES, ROOMS OR SPACES
 THAT CONTAIN A COOKING FACILITY WITH DOMESTIC COOKING
 APPLIANCES SHALL BE PERMITTED TO BE OPEN TO THE
 CORRIDOR WHERE ALL OF THE FOLLOWING CRITERIA ARE MET:
  
 1.THE NUMBER OF CARE RECIPIENTS HOUSED IN THE SMOKE
 COMPARTMENT IS NOT GREATER THAN 30.
  
 2.THE NUMBER OF CARE RECIPIENTS SERVED BY THE COOKING
 FACILITY IS NOT GREATER THAN 30.
  
 3.ONLY ONE COOKING FACILITY AREA IS PERMITTED IN A
 SMOKE COMPARTMENT.
  
 4.THE TYPES OF DOMESTIC COOKING APPLIANCES PERMITTED
 ARE LIMITED TO OVENS, COOKTOPS, RANGES, WARMERS AND
 MICROWAVES.
  
 5.THE CORRIDOR IS A CLEARLY IDENTIFIED SPACE DELINEATED
 BY CONSTRUCTION OR FLOOR PATTERN, MATERIAL OR COLOR.
  
 6.THE SPACE CONTAINING THE DOMESTIC COOKING FACILITY
 SHALL BE ARRANGED SO AS NOT TO OBSTRUCT ACCESS TO THE
 REQUIRED EXIT.
  
 7.A DOMESTIC COOKING HOOD INSTALLED AND CONSTRUCTED IN
 ACCORDANCE WITH SECTION 505 OF THE FLORIDA BUILDING
 CODE, MECHANICAL IS PROVIDED OVER THE COOKTOP OR RANGE.
  
 8.THE DOMESTIC COOKING HOOD PROVIDED OVER THE COOKTOP
 OR RANGE SHALL BE EQUIPPED WITH AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM OF A TYPE RECOGNIZED FOR
 PROTECTION OF DOMESTIC COOKING EQUIPMENT. PREENGINEERED
 AUTOMATIC EXTINGUISHING SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH UL 300A AND LISTED AND LABELED FOR THE
 INTENDED APPLICATION. THE SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH THIS CODE, ITS LISTING AND THE
 MANUFACTURER'S INSTRUCTIONS.
  
 9.A MANUAL ACTUATION DEVICE FOR THE HOOD SUPPRESSION
 SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH SECTIONS
 904.12.1 AND 904.12.2.
  
 10.AN INTERLOCK DEVICE SHALL BE PROVIDED SUCH THAT UPON
 ACTIVATION OF THE HOOD SUPPRESSION SYSTEM, THE POWER OR
 FUEL SUPPLY TO THE COOKTOP OR RANGE WILL BE TURNED OFF.
  
 11.A SHUT-OFF FOR THE FUEL AND ELECTRICAL POWER SUPPLY
 TO THE COOKING EQUIPMENT SHALL BE PROVIDED IN A
 LOCATION THAT IS ACCESSIBLE ONLY TO STAFF.
  
 12.A TIMER SHALL BE PROVIDED THAT AUTOMATICALLY
 DEACTIVATES THE COOKING APPLIANCES WITHIN A PERIOD OF
 NOT MORE THAN 120 MINUTES.
  
 13.A PORTABLE FIRE EXTINGUISHER SHALL BE INSTALLED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved