2019-04-08 08:44:48 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. REVISION PROVIDED DOES NOT INDICATE THE CHANGES FROM |
| THE ORIGINAL PLAN. REVISIONS TO PLAN SHOULD BE CLOUDED |
| FOR IDENTIFICATION AND EXPLAINED IN DETAIL. SIMPLY |
| STATING "AS BUILT" ON THE PLAN IS NOT ACCEPTABLE. |
| PROVIDE CORRECTION. WPB FBC 107.2.1 |
| 2. IT APPEARS THAT THERE HAS BEEN SUBSTANTIAL WORK |
| ADDED, BUT THE LOAD CALCULATION IS THE SAME AS BEFORE. |
| INCLUDE CORRECTED LOAD CALCULATION SHOWING ALL LOADS. |
| NEC 220; FBC RE E3602.2 |
| 3. IT APPEARS THAT THERE HAS BEEN SUBSTANTIAL WORK |
| ADDED, BUT THE SUBMITTAL FORM STATES THAT THERE IS NO |
| ADDED VALUE. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE |
| AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. |
| THIS IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| 109.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |