2019-06-12 13:30:56GAS 2ND REVIEW**DENIED**
  
  
 1) ANSWERED**
  
 2) ANSWERED**
  
 3) ANSWERED**
  
 4) ANSWERED**
  
 5) PLEASE PROVIDE MEASUREMENTS AND ALL PIPING USED FOR
 EACH SECTION OF PIPING .SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 6) PARTIAL SEE COMMENT #5.SHOW THE TYPE OF PIPE
 MATERIAL BEING INSTALLED, ALL PIPE SIZES, AND THE
 CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS
 STEEL TUBING (IF APPLICABLE) FOR EACH PIPE SIZE. WPB
 AMENDMENTS TO FBC SEC.107.2.1.
  
 7) NOT ADDRESSED. THIS IS THE SUBMITTAL PHASE PLEASE
 SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THE GAS GENERATOR TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3
  
 NEW COMMENT'S
  
 8) SYSTEM IS CALLED OUT AS .5LB BUT YOU SHOW A PRESSURE
 REGULATOR ON THE CONNECTION DETAIL. PLEASE CLARIFY. FBC
 107.2.1
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1,
  
 10) PRESSURE REGULATORS SHALL BE INSTALLED PER FBC-GAS
 410.2
  
 (A) A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED BETWEEN THE MP REGULATOR AND ITS
 UPSTREAM SHUTOFF VALVE.
  
 (B) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT (304 MM) OF EITHER SIDE OF THE
 MP REGULATOR.
  