Date |
Text |
2019-06-12 13:30:56 | GAS 2ND REVIEW**DENIED** |
| |
| |
| 1) ANSWERED** |
| |
| 2) ANSWERED** |
| |
| 3) ANSWERED** |
| |
| 4) ANSWERED** |
| |
| 5) PLEASE PROVIDE MEASUREMENTS AND ALL PIPING USED FOR |
| EACH SECTION OF PIPING .SUBMIT AN ISOMETRIC DRAWING |
| THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF |
| PIPE PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. |
| |
| 6) PARTIAL SEE COMMENT #5.SHOW THE TYPE OF PIPE |
| MATERIAL BEING INSTALLED, ALL PIPE SIZES, AND THE |
| CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS |
| STEEL TUBING (IF APPLICABLE) FOR EACH PIPE SIZE. WPB |
| AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 7) NOT ADDRESSED. THIS IS THE SUBMITTAL PHASE PLEASE |
| SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR THE GAS GENERATOR TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 |
| |
| NEW COMMENT'S |
| |
| 8) SYSTEM IS CALLED OUT AS .5LB BUT YOU SHOW A PRESSURE |
| REGULATOR ON THE CONNECTION DETAIL. PLEASE CLARIFY. FBC |
| 107.2.1 |
| |
| 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2014 FGC SEC.410.1, |
| |
| 10) PRESSURE REGULATORS SHALL BE INSTALLED PER FBC-GAS |
| 410.2 |
| |
| (A) A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED |
| SHALL BE INSTALLED BETWEEN THE MP REGULATOR AND ITS |
| UPSTREAM SHUTOFF VALVE. |
| |
| (B) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE |
| INSTALLED WITHIN 1 FOOT (304 MM) OF EITHER SIDE OF THE |
| MP REGULATOR. |
| |