2019-04-10 14:32:32GAS 1ST REVIEW**DENIED**
  
 1) GENERATORS ARE REQUIRED TO HAVE THERE OWN PERMIT AND
 NOT BE A SUB OFF OF MASTER PERMIT. NOTE MASTER PLAN
 DOES NOT SHOW GENERATOR
  
 2) VALUE SEEMS LOW AND MUST INCLUDE THE COST OF THE
 GENERATOR. WPB AMEND TO THE FBC 109.3
  
 3) STEEL PIPING IS NOT PERMITTED UNDERGROUND. FBC-G
 404.11.1
  
 4) PRIVATE PROVIDER PAPERWORK HAS NOT BEEN INCLUDE IN
 THIS SUBMITTAL. FBC 107.3.5
  
 5) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2.
  
 6) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 7) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  