2019-05-31 11:47:04 | 5/31/19 |
| |
| |
| 1) THE APPLICATION INDICATES THE INSTALLATION OF A |
| GENERATOR & ATS. |
| |
| PER NFPA 37 |
| |
| 4.6* GENERAL INSTALLATION REQUIREMENTS. ENGINES AND |
| THEIR |
| APPURTENANCES SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| FOLLOWING: |
| (1) APPLICABLE NFPA CODES AND STANDARDS |
| (2) INDUSTRY STANDARDS |
| (3) USER REQUIREMENTS |
| (4) MANUFACTURER?S INSTALLATION INSTRUCTIONS |
| (5)*APPLICABLE LOCAL BUILDING CODES WITH RESPECT TO |
| WIND AND |
| SEISMIC DESIGN REQUIREMENTS. |
| |
| 1A) THERE ARE NO GENERATOR DETAILS. |
| |
| PER NFPA 110 |
| |
| CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY |
| SYSTEMS (EPSSS) |
| 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF |
| ELECTRICAL |
| POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO |
| LOADS FOR |
| A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND |
| WITHIN A SPECIFIED |
| TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER |
| SUPPLY |
| AS SPECIFIED IN TABLE 4.1(B). |
| |
| |
| 1B) THERE ARE NO ATS DETAILS |
| |
| PER NFPA 110 CHAPTER 6 TRANSFER SWITCH EQUIPMENT |
| 6.1 GENERAL. |
| 6.1.1* SWITCHES SHALL TRANSFER ELECTRIC LOADS FROM ONE |
| POWER |
| SOURCE TO ANOTHER. |
| 6.1.2* THE ELECTRICAL RATING SHALL BE SIZED FOR THE |
| TOTAL LOAD THAT |
| IS DESIGNED TO BE CONNECTED. |
| 6.1.3 EACH SWITCH SHALL BE IN A SEPARATE ENCLOSURE OR |
| COMPARTMENT. |
| 6.1.4 THE SWITCH, INCLUDING ALL LOAD CURRENT-CARRYING |
| COMPONENTS, |
| SHALL BE LISTED FOR ALL LOAD TYPES TO BE SERVED. |
| 6.1.5 THE SWITCH, INCLUDING ALL LOAD CURRENT-CARRYING |
| COMPONENTS, |
| SHALL BE DESIGNED TO WITHSTAND THE EFFECTS OF AVAILABLE |
| FAULT CURRENTS. |
| |
| PLEASE REVIEW AND CORRECT OR PROVIDE DETAILED |
| JUSTIFICATIONS. |
| |
| |
| |
| |
| 2) THE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA |
| CODES. |
| |
| NFPA 37 AND 110 ARE THE MINIMUM CODES OF COMPLAINCE. |
| |
| PLEASE REVIEW AND ENSURE COMPLAINCE AND PROVIDE AN |
| APPLICABLE NOTE. |
| |
| |
| |
| 3) THERE ARE NO INDICATIONS OF WHERE THE EXHAUST IS |
| LOCATED, AT WHAT HEIGHT IT ENDS AT, ANY DIMENSION TO |
| OPENINGS THAT MAY BE APPLICABLE TO THE ABOVE NOTED |
| CODES. |
| |
| |
| |
| PER NFPA 110 |
| |
| 7.10 EXHAUST SYSTEM. |
| 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION, |
| INCLUDING |
| PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN |
| ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION |
| AND USE OF |
| STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND |
| OTHER APPLICABLE |
| STANDARDS. |
| |
| NFPA 37 |
| |
| |
| |
| PLEASE REVIEW AND PROVIDE DETAILS. |
| |
| |
| |
| 4) THERE ARE NO MANUFACTURES SPEC SHEETS PROVIDED. |
| |
| PLEASE PROVIDE SPEC SHEETS FOR VERIFICATION PURPOSES. |
| |
| |
| |
| 5) THERE ARE NO INDICATIONS OF HOW THE GENERATOR WILL |
| BE SECURED TO THE SLAB. |
| |
| 7.4 MOUNTING. |
| 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON |
| SOLID |
| FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST, OR |
| LUBRICATINGOIL |
| PIPING AND DAMAGE TO PARTS RESULTING IN LEAKAGE AT |
| JOINTS. |
| |
| 7.5* VIBRATION. VIBRATION ISOLATORS, AS RECOMMENDED BY |
| THE |
| MANUFACTURER OF THE EPS, SHALL BE INSTALLED EITHER |
| BETWEEN THE |
| ROTATING EQUIPMENT AND ITS SKID BASE OR BETWEEN THE |
| SKID BASE |
| AND THE FOUNDATION OR INERTIA BASE. |
| |
| PLEASE PROVIDE DETAILS OR JUSTIFY. |
| |
| |
| |
| 6) THERE ARE NO INDICATIONS OF ELECTRICAL PROTECTIONS |
| |
| PER NFPA 37 |
| |
| 4.5.4 BATTERIES, WIRING, AND ELECTRICAL DEVICES SHALL |
| BE PROTECTED |
| AGAINST ARCING AND ACCIDENTAL SHORTING. |
| |
| |
| PER NFPA 110 |
| |
| 6.5 PROTECTION. |
| 6.5.1* GENERAL. THE OVERCURRENT PROTECTIVE DEVICES IN |
| THE EPSS |
| SHALL BE COORDINATED TO OPTIMIZE SELECTIVE TRIPPING OF |
| THE CIRCUIT |
| OVERCURRENT PROTECTIVE DEVICES WHEN A SHORT CIRCUIT |
| OCCURS. |
| |
| PLEASE PROVIDE DETAILS |
| |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |