2019-06-13 08:20:03BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19040257
 REVIEWED: JUNE 13, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
  
 1. 107.5.3 FBC[AMENDED] SHEET PD2 DOESN?T SHOW THE
 GENERATOR. PLEASE SHOW HOW GENERATOR AND PAD WORK WITH
 CIVIL PLAN AT DRAIN S-16.
  
 2. 1601.1 FBC[B] PROVIDE DETAIL TO SHOW HOW GENERATOR
 CONNECTS TO PAD.
  
 3. PROVIDE SPECIFICATIONS FOR THE GENERATOR.
  
 4. IF SCREENING IS ADDED THEN SHOW DETAILS FOR
 ATTACHMENT AND WIND DESIGN.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  