Plan Review Notes For Permit 19040257 |
Permit Number |
19040257 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-13 08:20:03 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT: 19040257 | | REVIEWED: JUNE 13, 2019 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER PX4191 | | [email protected] | | 561-805-6718 | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC[B] = FBC BUILDING | | | | 1. 107.5.3 FBC[AMENDED] SHEET PD2 DOESN?T SHOW THE | | GENERATOR. PLEASE SHOW HOW GENERATOR AND PAD WORK WITH | | CIVIL PLAN AT DRAIN S-16. | | | | 2. 1601.1 FBC[B] PROVIDE DETAIL TO SHOW HOW GENERATOR | | CONNECTS TO PAD. | | | | 3. PROVIDE SPECIFICATIONS FOR THE GENERATOR. | | | | 4. IF SCREENING IS ADDED THEN SHOW DETAILS FOR | | ATTACHMENT AND WIND DESIGN. | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | [email protected] | | | | | | |
|