2019-04-18 10:19:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040235
 4/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 WITH CORRESPONDING DRAWINGS AND DETAILS- SECTION
 107.2.1 WPB.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 RANGE AND EXHAUST HOOD, AND ANY OTHER NEW COOKING
 APPLIANCES- SECTIONS 505.1 AND 917.1 FBC M. PLEASE SEE
 SECTION 505.2 PRINTED BELOW AND SHOW COMPLIANCE.
  
 505.2 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CFM (0.19 M3/S) SHALL BE PROVIDED WITH MAKEUP AIR
 AT A RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE.
 SUCH MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH A MEANS
 OF CLOSURE AND SHALL BE AUTOMATICALLY CONTROLLED TO
 START AND OPERATE SIMULTANEOUSLY WITH THE EXHAUST
 SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  