Plan Review Notes
Plan Review Notes For Permit 19040215
Permit Number 19040215
Review Stop P
Sequence Number 2
Notes
Date Text
2019-06-20 13:19:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
 ORIGINAL COMMENTS
 1. COMPLIED
 2. COMPLIED
 3. COMPLIED
 4. REQUIRES FURTHER CLARIFICATION; PLAN SHEET G1101,
 PLUMBING FIXTURE COUNT CHART, INDICATES THAT ONE (1)
 SERVICE (MOP) SINK IS REQUIRED FOR THE BUILDING WHICH
 IS CORRECT. THE PLUMBING FIXTURE COUNT CHART INDICATES
 THERE ARE THREE (3) SERVICE (MOP) SINKS IN THE BUILDING
 WHICH EXCEEDS THE REQUIREMENTS OF FBC PL 403, TABLE
 403.1. HOWEVER, CHART REFERENCES THE FLORIDA PLUMBING
 CODE 2010. PER WPB FBC 107.2.1, REFENCE THE FLORIDA
 BUILDING CODE, PLUMBING 2017. ADDITIONALLY, REFLECT
 CONFIRM THE ACTUAL FIXTURE COUNT FOR THE BUILDING AND
 ACCURATELY REFLECT ON THE CHART.
 5. CLARIFIED
 6. CLARIFIED; THERE IS NO MOP SINK NEW OR EXISTING
 SHOWN IN ROOM 158.
 7. DID NOT COMPLY; TO BE CLEAR, THE WATER RISER DIAGRAM
 SHOWN ON P-2 ADDRESSES THE TOILET ROOMS 158 AND 159
 BUT, DOES NOT ADDRESS THE SERVICE BAR ROOM 193. PER WPB
 FBC 107.2.1, PROVIDE WATER RISER DIAGRAM TO ADDRESS
 THIS ROOM.
 8. COMPLIED
 9. COMPLIED
 10. DID NOT COMPLY. TEMPERED WATER IS REQUIRED TO THE
 LAVATORIES PER FBC-PLUMBING SEC.416.5. PER WPB FBC
 107.2.1, PROVIDE NOTE REQUIRING TEMPERED WATER FOR THE
 LAVATORIES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC
 PL 416.5.
  
 NEW COMMENTS
 1. RE: P-2 SANITARY RISER DIAGRAM; EACH WET-VENTED
 FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE
 HORIZONTAL WET VENT PER FBC PL 912.1. TO BE CLEAR, THE
 FLOOR DRAIN SHALL NOT CONNECT TO THE WATER CLOSET AHEAD
 OF THE VENT. CONNECT DOWNSTREAM OF VERTICAL PORTION OF
 THE WET VENT. PER WPB FBC 107.2.1, SHOW ON P-2,
 SANITARY RISER DIAGRAM AND ON P-3, SANITARY PLUMBING
 PLAN.
 2. PER WPB FBC 107.2.1, PROVIDE SANITARY RISER DIAGRAM
 TO ADDRESS THE SERVICE BAR ROOM 193.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19040215 8225 IBIS BLVD
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved