Date |
Text |
2019-06-20 13:19:10 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 30A |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 2ND REVIEW |
| PLUMBING COMMEMTS: DENIED |
| ORIGINAL COMMENTS |
| 1. COMPLIED |
| 2. COMPLIED |
| 3. COMPLIED |
| 4. REQUIRES FURTHER CLARIFICATION; PLAN SHEET G1101, |
| PLUMBING FIXTURE COUNT CHART, INDICATES THAT ONE (1) |
| SERVICE (MOP) SINK IS REQUIRED FOR THE BUILDING WHICH |
| IS CORRECT. THE PLUMBING FIXTURE COUNT CHART INDICATES |
| THERE ARE THREE (3) SERVICE (MOP) SINKS IN THE BUILDING |
| WHICH EXCEEDS THE REQUIREMENTS OF FBC PL 403, TABLE |
| 403.1. HOWEVER, CHART REFERENCES THE FLORIDA PLUMBING |
| CODE 2010. PER WPB FBC 107.2.1, REFENCE THE FLORIDA |
| BUILDING CODE, PLUMBING 2017. ADDITIONALLY, REFLECT |
| CONFIRM THE ACTUAL FIXTURE COUNT FOR THE BUILDING AND |
| ACCURATELY REFLECT ON THE CHART. |
| 5. CLARIFIED |
| 6. CLARIFIED; THERE IS NO MOP SINK NEW OR EXISTING |
| SHOWN IN ROOM 158. |
| 7. DID NOT COMPLY; TO BE CLEAR, THE WATER RISER DIAGRAM |
| SHOWN ON P-2 ADDRESSES THE TOILET ROOMS 158 AND 159 |
| BUT, DOES NOT ADDRESS THE SERVICE BAR ROOM 193. PER WPB |
| FBC 107.2.1, PROVIDE WATER RISER DIAGRAM TO ADDRESS |
| THIS ROOM. |
| 8. COMPLIED |
| 9. COMPLIED |
| 10. DID NOT COMPLY. TEMPERED WATER IS REQUIRED TO THE |
| LAVATORIES PER FBC-PLUMBING SEC.416.5. PER WPB FBC |
| 107.2.1, PROVIDE NOTE REQUIRING TEMPERED WATER FOR THE |
| LAVATORIES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC |
| PL 416.5. |
| |
| NEW COMMENTS |
| 1. RE: P-2 SANITARY RISER DIAGRAM; EACH WET-VENTED |
| FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE |
| HORIZONTAL WET VENT PER FBC PL 912.1. TO BE CLEAR, THE |
| FLOOR DRAIN SHALL NOT CONNECT TO THE WATER CLOSET AHEAD |
| OF THE VENT. CONNECT DOWNSTREAM OF VERTICAL PORTION OF |
| THE WET VENT. PER WPB FBC 107.2.1, SHOW ON P-2, |
| SANITARY RISER DIAGRAM AND ON P-3, SANITARY PLUMBING |
| PLAN. |
| 2. PER WPB FBC 107.2.1, PROVIDE SANITARY RISER DIAGRAM |
| TO ADDRESS THE SERVICE BAR ROOM 193. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19040215 8225 IBIS BLVD |
| |
| |