2019-05-07 11:55:08 | 1) SHT.AE-5.01 - THE TOILET PAPER DISPENSER FOR THE |
| ACCESSIBLE WATER CLOSET SHALL BE LOCATED 7 INCHES |
| MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER |
| CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. |
| 2017 FBC - ACCESS. SEC.604.7. |
| 2) SHT. AE-5.01 -THE FLUSH HANDLE FOR THE ACCESSIBLE |
| WATER CLOSET SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| TOILET. THE DETAIL SHOWS THE HANDLE ON THE WALL SIDE. |
| 2017 FBC - ACCESS. SEC. 604.6. |
| 3) SHT. AE-5.01 - THE RIM OF THE URINAL SHALL BE |
| LOCATED A MAXIMUM OF 17 INCHES ABOVE THE FINISH FLOOR. |
| 2017 FBC-ACCESS. SEC.605.2. THE URINAL SHALL BE 13 1/2 |
| INCHES DEEP MINIMUM MEASURED FROM THE OUTER FACE OF THE |
| URINAL RIM TO THE BACK OF THE FIXTURE. |
| 4) SHT. P-2 SHOWS THE MOP SINK TO BE REMOVED. A MOP |
| SINK IS A REQUIRED FIXTURE FOR THIS OCCUPANCY |
| CLASSIFICATION PER TABLE 403.1 OF THE FBC-PLUMBING. |
| 5) SHT.P-3 IS VAGUE AS TO THE SCOPE OF PLUMBING WORK |
| BEING DONE. CLEARLY SHOW ON THE PLAN THE SCOPE OF WORK |
| THAT IS BEING DONE. SHOW WHICH PLUMBING & FIXTURES ARE |
| EXISTING TO REMAIN, EXISTING TO BE REMOVED AND WHAT IS |
| NEW. IS ANY PLUMBING BEING ALTERED IN TOILET ROOMS |
| #158? WPB AMEND. TO FBC SEC. 107.2.1. |
| 6) SHT P-3 - IS THE MOP SINK IN STORAGE ROOM #158 NEW |
| OR EXISTING? CLARIFY ON THE PLANS. |
| 7) SUBMIT A WATER RISER DIAGRAM FOR ANY NEW WATER |
| PIPING TO INSTALLED. WPB AMEND.TO FBC SEC.107.3.5.1.3. |
| 8) SHT.P-2 - THE SANITARY RISER SHOWS A 4 INCH VENT FOR |
| A 3 INCH SANITARY DRAIN. CLARIFY. |
| 9) SHT. P-2 - THE SANITARY RISER FOR THE TOILET ROOMS |
| SHOWS AN 1 1/2 INCH VENT FOR THE LAVATORY AND WATER |
| CLOSET. THE DRAIN IS SHOWN AS 4 INCH. THE VENT SHALL |
| NOT BE LESS THAN ONE-HALF THE SIZE OF THE DRAIN SERVED. |
| 2017 FBC-PLUMBING SEC.906.1. |
| 10) TEMPERED WATER IS REQUIRED TO THE LAVATORIES PER |
| FBC-PLUMBING SEC.416.5. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |