2019-05-08 17:43:09 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19040215 |
| 5/8/2019 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M3: THE OUTDOOR AIR RATE TABLE IS INCORRECTLY |
| INDICATING THE MINIMUM O/A CFMS AT 262, HOWEVER THE |
| MINIMUM RATE IS 4341 WHICH IS LISTED AS THE MAXIMUM IN |
| THE TABLE- REFER TO TABLE 403.3.1.1 FBC M. PLEASE |
| PROVIDE THE SPECIFIC FBC M OR ASHRAE CODE SECTION USED |
| AS REFERENCE FOR THE DESIGN VENTILATION SYSTEM AND NOTE |
| #2 UNDER THE TABLE. |
| |
| 2) SHEETS G1101 & M5: PLEASE CLARIFY IF THE WALLS |
| ENCLOSING THE MECHANICAL ROOMS ARE FIRE-RATED, OR ANY |
| OTHER WALLS THAT ARE BEING PENETRATED BY DUCTS- SECTION |
| 107.2.1 WPB AND SECTION 607 FBC M. |
| |
| 3) M5: PLEASE PLACE NOTES AND SYMBOLS ON THE PLANS TO |
| INDICATE THE LOCATIONS OF THE REQUIRED DUCT SMOKE |
| DETECTORS IN THE SUPPLY SYSTEMS OF AHU 1-1 AND AHU 1-4, |
| AND THE REQUIRED O/A DAMPERS FOR THE SYSTEMS- SEE |
| SECTIONS 606.2.1 FBC M, AND SECTION C403.2.4.3 FBC EC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |