Date |
Text |
2019-04-12 13:52:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET AE601 - THERE ARE NO INDICATIONS OF REQUIRED |
| EXIT HARDWARE ON DOORS WITHIN A MEANS OF EGRESS; |
| |
| DOOR(S) 188A, 188B 118A, 184, 169B |
| |
| PER NFPA 101, CHAPTER 12: |
| |
| 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| AN AREA HAVING |
| AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| PERMITTED TO BE |
| PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| IS PANIC |
| HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| UNLESS |
| OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| LOCKS AS |
| PERMITTED IN 12.2.2.2.5. |
| (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| ACCESS-CONTROLLED EGRESS DOORS |
| AS PERMITTED IN 12.2.2.2.6. |
| 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| SHALL BE PERMITTED |
| TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| IF BOTH OF THE |
| FOLLOWING CONDITIONS APPLY: |
| (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| AND THE ASSEMBLY |
| OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| ASSEMBLY |
| OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| RELEASED |
| BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| |
| |
| |
| 2) SHEET AE601 - THERE ARE INDICATIONS OF HOLD OPEN ON |
| SEVERAL DOORS. |
| |
| DOES THIS INDICATE MAG-LOCKS TIED INTO THE FIRE ALARM. |
| |
| PLEASE REVIEW AND CLARIFY OR CORRECT. |
| |
| |
| |
| 3) SHEET AE 401 - THERE ARE DOORS INDICATED ON SHEETS |
| AE 401 & AE 402 WITH FIRE RATED WALLS. THE DOOR |
| SCHEDULE DOES NOT INDICATE ANY RATING ON THE DDORS. |
| |
| THE FOLLOWING DOORS ARE, BUT MAY NOT BE LIMITED TO : |
| 188A & B, 184, 169B, 160. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WHAY THE RATINGS |
| ARE NOT REQUIRED. |
| |
| PLEASE BE SURE TO CHECK ALL THE DOORS TO ENSURE ALL |
| DOORS WITHIN FIRE RATED WALLS CARRY THE REQUIRED |
| RATING. |
| |
| |
| |
| |
| 4) SHEET E 1 - THERE ARE INDICATIONS OF FIRE ALARM |
| EQUIPEMNT DEVICES IN THE SYMBOL AND LEGEND AREA. |
| COMMNET # 32 INDICATES FIRE ALARM MANUFACTURER |
| INFORMATION. |
| |
| IT DOES NOT INDICATE THAT ANY WORK ON THE FIRE ALARM |
| SYSTEM SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP |
| DRAWINGS BY CERTIFIED FIRE ALARM CONTRACTORS. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGEMENT. |
| |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |