2019-05-15 09:26:32 | RESIDENTIAL (R3) RE-ROOF, THIRD BUILDING REVIEW | | CHECKLIST. | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R23 | | SUBMITTED: | | A) SELECTED ASSEMBLY W-104 DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED | | AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY | | LIMITATION #5.7 ON PAGE 5 OF 6 OF PRODUCT APPROVAL | | SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN | | PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|