2019-05-06 08:58:35 | RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R22 |
| SUBMITTED: |
| A) SELECTED ASSEMBLY W-104 DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED |
| AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY |
| LIMITATION #5.7 ON PAGE 5 OF 6 OF PRODUCT APPROVAL |
| SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN |
| PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| NOTE: CONTRACTOR MAY SELECT ANOTHER ASSEMBLY THAT MEETS |
| THE DESIGN PRESSURES FOR ALL ROOF ZONES AND RAS 117 |
| CALCULATIONS ARE NOT REQUIRED. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| B) PROVIDE CURRENT FLORIDA PRODUCT APPROVAL. CURRENT |
| FLORIDA PRODUCT APPROVAL IS FL1654-R23 NOT FL1654-R22. |
| FAC 61G20-3.001. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| C) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT |
| APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT |
| SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL |
| STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- METAL ROOFING PANELS WERE CHANGED TO SHINGLES |
| BECAUSE HISTORIC DOESN'T ALLOW METAL ROOFING PANELS. |
| THE FOLLOWING REQUIRED INFORMATION WAS NOT SUBMITTED AS |
| REQUESTED ON PREVIOUS CHECKLIST: |
| |
| A) SPECIFY ROOF PITCH AND ROOF MEAN ROOF HEIGHT AS |
| REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS AND |
| SEC. R905.10.2 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| B) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT |
| APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT |
| SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL |
| STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 3- ROOF UNDERLAYMENT FL21895-R2 SUBMITTED: PROVIDE |
| COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT APPROVAL |
| SUBMITTED IS MISSING THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE. THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE |
| CURRENT CODE VERSION AND THE PRODUCT APPROVAL STATUS. |
| CHAPTER 553 F.S. AND FAC 61G20-3.001. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 4- THERE IS MORE THAN ONE STRUCTURE IN THIS PROPERTY. |
| PROVIDE MAP OR SKETCH SHOWING LOCATION OF AREA OF WORK |
| AND SQUARE FOOTAGE OF EACH AREA (PITCH AND FLAT) AS |
| REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS AND |
| SEC. 107.02.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. VALUATION WILL BE RE-EVALUATED ONCE THE |
| ROOFING AREAS ARE PROVIDED. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |